Display | Meaning | Corrective Actions | |
| Function Selection Error |
| |
OPE08 | A setting has been made that is applicable with the cur- |
| |
rent control method. | Verify the control method and the function. | ||
Constant Selection | |||
| Example: A function used only with open loop vector |
| |
| control was selected for V/f control. |
| |
|
|
| |
OPE010 | V/f Parameter Setting Error | Check parameters | |
V/f Ptrn Setting | may be set higher than the maximum frequency/voltage. | ||
| |||
|
|
|
Autotuning Faults
Autotuning faults are shown below. When the following faults are detected, the fault is displayed on the digital operator and the motor coasts to stop. No fault or alarm outputs will be operated.
Display | Meaning | Corrective Actions | |
|
| • Check the input data. | |
Motor data fault | • Check the Inverter and motor capacity. | ||
Fault | • Check the motor rated current and | ||
| |||
|
| ting. | |
|
|
| |
| • Check the input data. | ||
Alarm | • Check wiring and the machine. | ||
Minor Fault | |||
| • Check the load. | ||
|
| ||
|
|
| |
STOP key input | - | ||
STOP key | |||
|
| ||
|
|
| |
| |||
Autotuning result is outside the parameter setting |
| ||
Resistance |
| ||
range. | • Check the input data. | ||
| |||
• Check the motor wiring. | |||
Autotuning result is outside the parameter setting | • If the motor is connected to the machine, disconnect it. | ||
| range. | • If the setting of | |
|
| power supply voltage | |
Rated Slip Fault | |||
Autotuning result is outside the parameter setting |
| ||
Rated slip |
| ||
range. |
| ||
|
| ||
|
|
| |
Acceleration Fault (Rotating autotuning only) | • Increase | ||
The motor did not accelerate in the specified time | • Increase | ||
Accelerate | |||
• If the motor is connected to the machine, disconnect it. | |||
| |||
|
|
| |
| Motor Speed Fault (Rotating autotuning only) | • If the motor is connected to the machine, disconnect it. | |
The torque reference exceeded 100% during accel- | • Increase | ||
Motor Speed | eration. Deteceted only when | • Check the input data (particularly the number of PG | |
| control modes). | pulses and the number of motor poles) | |
|
|
| |
Current Detection Fault |
| ||
• The current exceeded the motor rated current. | Check wiring of the Inverter and the mounting. | ||
• Any of U/T1, V/T2 and W/T3 has |
| ||
|
| ||
|
|
| |
Leakage Inductance Fault |
| ||
Leakage Induc- | Autotuning result is outside the parameter setting | Check motor wiring. | |
tance Fault | range. |
| |
|
|
| |
| Rated Current Setting Alarm |
| |
Displayed after | Check the motor rated current value. | ||
V/f Over Setting | During | ||
| |||
| rated current |
| |
|
|
| |
Motor Core Saturation Alarm | • Check the input data | ||
• Check the motor wiring. | |||
Saturation | (only for rotating autotuning) | ||
• If the motor is connected to the machine, disconnect it. | |||
|
| ||
|
|
| |
Rated Current Setting Alarm |
| ||
During autotuning the measured value of motor rated | Check the motor rated current value | ||
Rated FLA Alm | |||
current |
| ||
|
| ||
|
|
|