Omron Healthcare VARISPEEDF7 specifications EN-22, OH1, OL1, OL2, Pgo

Models: VARISPEEDF7

1 25
Download 25 pages 7.4 Kb
Page 23
Image 23

Display

Alarm

Fault

Meaning

 

Corrective Actions

 

 

 

 

Remove the motor and run the Inverter

 

 

 

 

 

without the motor.

OC

 



Over Current

Check the motor for a phase-to-phase

 

The Inverter’s output current exceeded the over-

 

short.

Over Current

 

 

 

 

current detection level.

Verify the accel/decel times (C1-††).

 

 

 

 

 

 

 

Check the Inverter for a phase-to-phase

 

 

 

 

 

short at the output.

 

 

 

 

 

 

 

 

 

Heatsink Overheat

Check for dirt build-up on the fans or heat-

 

 



L8-03 = 0,1 or 2 and the temperature of the

 

 

 

sink.

OH

 

Inverter's cooling fin exceeded the L8-02 value.

 

 

 

 

Reduce the ambient temperature around

 

 

Inverter's Cooling Fan Stopped

Heatsnk Overtemp

 

 

 

the drive.

 

 

 

 

 

 

L8-03 = 3 or 4 and the temperature of the

 

 



 

Replace the cooling fan(s).

 

 

Inverter's cooling fin exceeded the L8-02 value.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heatsink Overheat

Check for dirt build-up on the fans or heat-

OH1

 



The temperature of the Inverter’s heatsink

 

sink.

 

exceeded 105 °C.

Reduce the ambient temperature around

Heatsink Max Temp

 

 

 

 

 

the drive.

 

 

 

Inverter’s Cooling Fan Stopped

 

 

 

 

Replace the cooling fan(s).

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor Overload

 

 

 

 

 

Detected when L1-01 is set to 1,2 or 3 and the

Recheck the cycle time and the size of the

 

 

 

Inverter’s I²t value exceeded the motor overload

 

load as well as the accel/decel times (C1-

 

 

 

curve.

 

OL1

 



 

††).

 

The overload curve is adjustable using parame-

Motor Overload

 

 

ter

Check the V/f characteristics (E1-††).

 

 

 

Check the setting of Motor Rated Current

 

 

 

E2-01 (Motor Rated Current), L1-01 (Motor Pro-

 

 

 

tection Selection) and L2-02 (Motor Protection

 

Setting (E2-01).

 

 

 

 

 

 

 

 

Time Constant)

 

 

 

 

 

 

 

 

 

 

 

 

Recheck the cycle time and the size of the

 

 

 

Inverter Overload

 

load as well as the accel/decel times (C1-

OL2

 



 

††).

 

The Inverter output current exceeded the Invert-

Inv Overload

 

 

ers’s overload capability

Check the V/f Characteristics (E1-††).

 

 

 

Check if the inverter rated current matches

 

 

 

 

 

 

 

 

 

the motor rated current.

 

 

 

 

 

 

 

 

 

F1-03 = 0, 1 or 2 and A1-02 = 1 or 3

 

 

 

 



The motor speed feedback (U1-05) exceeded

 

 

 

 

the setting in F1-08 for a time longer than the

Adjust the ASR settings in the C5 parame-

 

 

 

setting of

 

 

 

 

ter groupt

OS

 

 

F1-09

 

 

 

Check the reference circuit and reference

Overspeed Det.

 

 

 

 

 

F1-03 = 3 and A1-02 = 1 or 3

 

 

 

gain.

 

 

 

The motor speed feedback (U1-05) exceeded

 

 



 

Check the settings in F1-08 and F1-09

 

 

the setting in F1-08 for a time longer than the

 

 

 

 

 

 

 

setting of

 

 

 

 

 

F1-09

 

 

 

 

 

 

 

 

 



 

The DC bus voltage has exceeded the overvolt-

Increase the deceleration time (C1-02/04)

 

 

age detection level.

 

or connect a braking option.

OV

(only in



Check the power supply and decrease the

stop

Default detection levels are:

DC Bus Overvolt

 

voltage to meet the inverter’s specifica-

condi-

 

200 V class: 410 VDC

 

 

 

 

tions.

 

tio)

 

400 V class: 820 VDC

 

 

 

Check the braking chopper / resistor.

 

 

 

 

 

 

 

 

 

 

PF

 



Input Phase Loss

Tighten the input terminal screws

 

Too big DC bus voltage ripple.

Input Phase Loss

 

Check the power supply voltage

 

 

Only detected when L8-05=1 (enabled)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PG Disconnection

 

 

 

 

 

Detected when F1-02 = 0, 1 or 2 and A1-02 = 1

 

 

 

 



or 3.

Fix the broken/disconnected wiring.

 

 

 

Detected when no PG (encoder) pulses have

Supply power to the PG properly.

PGO

 

 

been received for a time longer than the setting

PG Open

 

 

in F1-14.

Check the sequence and if the brake is

 

 

 

opened when the inverter starts to increase

 

 

 

 

 

 

 

 

PG Disconnection

 

 

 

 

 

the speed.

 

 

 

Detected when F1-02 = 3 and A1-02 = 1 or 3.

 

 



 

 

 

 

 

PG (encoder) pulses have not been received for

 

 

 

 

 

 

 

 

 

 

a time longer than the setting in F1-14.

 

 

 

 

 

 

 

 

EN-22

Page 23
Image 23