Display | Alarm | Fault | Meaning |
| Corrective Actions | |
|
|
|
| • | Remove the motor and run the Inverter | |
|
|
|
|
| without the motor. | |
OC |
| | Over Current | • | Check the motor for a | |
| The Inverter’s output current exceeded the over- |
| short. | |||
Over Current |
|
| ||||
|
| current detection level. | • | Verify the accel/decel times | ||
|
|
| ||||
|
|
|
| • | Check the Inverter for a | |
|
|
|
|
| short at the output. | |
|
|
|
|
|
| |
|
|
| Heatsink Overheat | • | Check for dirt | |
|
| | ||||
|
|
| sink. | |||
OH |
| Inverter's cooling fin exceeded the |
| |||
|
|
| • | Reduce the ambient temperature around | ||
|
| Inverter's Cooling Fan Stopped | ||||
Heatsnk Overtemp |
|
|
| the drive. | ||
|
|
|
| |||
|
|
| ||||
| |
| • | Replace the cooling fan(s). | ||
|
| Inverter's cooling fin exceeded the | ||||
|
|
|
|
| ||
|
|
|
|
|
| |
|
|
| Heatsink Overheat | • | Check for dirt | |
OH1 |
| | The temperature of the Inverter’s heatsink |
| sink. | |
| exceeded 105 °C. | • | Reduce the ambient temperature around | |||
Heatsink Max Temp |
| |||||
|
|
|
| the drive. | ||
|
|
| Inverter’s Cooling Fan Stopped |
| ||
|
|
| • | Replace the cooling fan(s). | ||
|
|
|
| |||
|
|
|
|
|
| |
|
|
| Motor Overload |
|
| |
|
|
| Detected when | • | Recheck the cycle time and the size of the | |
|
|
| Inverter’s I²t value exceeded the motor overload |
| load as well as the accel/decel times (C1- | |
|
|
| curve. |
| ||
OL1 |
| |
| ). | ||
| The overload curve is adjustable using parame- | • | ||||
Motor Overload |
|
| ter | Check the V/f characteristics | ||
|
|
| • | Check the setting of Motor Rated Current | ||
|
|
| ||||
|
|
| tection Selection) and |
| Setting | |
|
|
|
|
| ||
|
|
| Time Constant) |
|
| |
|
|
|
|
|
| |
|
|
|
| • | Recheck the cycle time and the size of the | |
|
|
| Inverter Overload |
| load as well as the accel/decel times (C1- | |
OL2 |
| |
| ). | ||
| The Inverter output current exceeded the Invert- | • | ||||
Inv Overload |
|
| ers’s overload capability | Check the V/f Characteristics | ||
|
|
| • | Check if the inverter rated current matches | ||
|
|
|
| |||
|
|
|
|
| the motor rated current. | |
|
|
|
|
|
| |
|
|
|
|
| ||
|
| | The motor speed feedback |
|
| |
|
| the setting in | • | Adjust the ASR settings in the C5 parame- | ||
|
|
| setting of | |||
|
|
|
| ter groupt | ||
OS |
|
|
| |||
|
| • | Check the reference circuit and reference | |||
Overspeed Det. |
|
|
| |||
|
| |||||
|
|
| gain. | |||
|
|
| The motor speed feedback |
| ||
| |
| • | Check the settings in | ||
|
| the setting in | ||||
|
|
|
| |||
|
|
| setting of |
|
| |
|
|
|
|
| ||
|
|
|
|
|
| |
| |
| The DC bus voltage has exceeded the overvolt- | • | Increase the deceleration time | |
|
| age detection level. |
| or connect a braking option. | ||
OV | (only in | | • | Check the power supply and decrease the | ||
stop | Default detection levels are: | |||||
DC Bus Overvolt |
| voltage to meet the inverter’s specifica- | ||||
condi- |
| 200 V class: 410 VDC |
| |||
|
|
| tions. | |||
| tio) |
| 400 V class: 820 VDC |
| ||
|
| • | Check the braking chopper / resistor. | |||
|
|
|
| |||
|
|
|
|
|
| |
PF |
| | Input Phase Loss | • | Tighten the input terminal screws | |
| Too big DC bus voltage ripple. | |||||
Input Phase Loss |
| • | Check the power supply voltage | |||
|
| Only detected when | ||||
|
|
|
|
| ||
|
|
|
|
|
| |
|
|
| PG Disconnection |
|
| |
|
|
| Detected when |
|
| |
|
| | or 3. | • | Fix the broken/disconnected wiring. | |
|
|
| Detected when no PG (encoder) pulses have | • | Supply power to the PG properly. | |
PGO |
|
| been received for a time longer than the setting | |||
PG Open |
|
| in | • | Check the sequence and if the brake is | |
|
|
| opened when the inverter starts to increase | |||
|
|
|
|
| ||
|
|
| PG Disconnection |
| ||
|
|
|
| the speed. | ||
|
|
| Detected when |
| ||
| |
|
|
| ||
|
| PG (encoder) pulses have not been received for |
|
| ||
|
|
|
|
| ||
|
|
| a time longer than the setting in |
|
| |
|
|
|
|
|
|