START-UP PROCEDURE

Optima 3600

29

OPERATION INSTRUCTIONS

START-UP PROCEDURE

1.

Set the thermostat, if present, to the lowest level. Set the remote switch to the OFF position.

 

Set the flame adjustment knob to the HI position. Press slightly and turn the control knob

 

clockwise 3 to the OFF position and wait 5 minutes; thus allowing any gases to escape which

 

may have accumulated in the combustion chamber.

 

Note: LP gases do not vent upward. Then follow step 2 and 3 to establish pilot.

2.

Press slightly and turn control knob counterclockwise 4 to PILOT position; depress control

 

knob and light pilot by repeatedly pressing the sparker. Venting of air may take place at the

 

pilot prior to the flow of fuel gases. Once flame is established, hold knob depressed in the

 

PILOT position for approximately 60 sec.

3.

Release knob. If pilot should go out, turn the control knob to OFF position and repeat steps 1,

 

2 and 3. Note: this will allow reset of INTERLOCK for proper lighting of pilot.

4.

Once the pilot is established, press and turn control knob counterclockwise 4 to ON position.

5.

Turn thermostat to the desired comfort level or turn the ON/OFF switch to the ON position.

6.

Turn flame and fan adjustment knob to the desired comfort level using HI / LOW knob.

TEMPORARY SHUT-DOWN PROCEDURE

To turn off the main burner only, set the thermostat to the lowest setting or turn remote switch to OFF. Press and turn the knob clockwise 3 to PILOT position.

COMPLETE SHUT-DOWN PROCEDURE

Press and turn the knob clockwise 3 to the OFF position.