Analog Input #6
This analog input is reserved for Duct Static Pressure. This value can then be used to
monitor the duct static or to actually control the duct static using an analog output and
driving either inlet vanes or a VFD controller. It is not recommended that you attempt to
use relays to control the duct static pressure, although this reading can be selected as a
control source on the relay configuration screen.
CAUTION: If you select two relays to control duct static, WattMaster
Controls cannot assume any liability for equipment
damage caused by over-pressurization of the duct work!
If you require a Duct Static Pressure Sensor, you must use an OE271 sensor provided by
WattMaster Controls for proper sensor readings. No other sensors are currently supported
for this input.
All setpoints related to duct static control pressures and alarm points are programmed on
this screen which activates when you left-click on the pressure reading box.