Relay Output #3 Programming ( Used for Boiler #2 )
The second boiler stage is enabled to operate if the water temperature is below 170°F and
will remain on until it rises to 180°F. The second stage can only operate if the first boiler
stage relay #2 has been active for at least 5 minutes. Once activated, this stage must
remain on for 5 minutes and once de-activated it must remain off for 10 minutes.