Orion Car Audio OE331-21 manual Relay Output #4 Programming Used for Boiler #3

Models: OE331-21

1 42
Download 42 pages 865.78 Kb
Page 31
Image 31

Relay Output #4 Programming ( Used for Boiler #3 )

The third boiler stage is enabled to operate if the water temperature is below 160°F and will remain on until it rises to 175°F. The third stage can only operate if the second boiler stage relay #3 has been active for at least 5 minutes. Once activated, this stage must remain on for 5 minutes and once de-activated it must remain off for 10 minutes.

25

Page 31
Image 31
Orion Car Audio OE331-21 manual Relay Output #4 Programming Used for Boiler #3