Analog OutputConfiguration
Two Proportional Outputs ( 0 - 10 VDC ) are available to the user. This output operates
using standard floating point control or a modified Proportional/Derivative control as
configured by the user. The controlling setpoint can be reset by any other sensor reading
or the outdoor air temperature and the output voltage range can be limited by the user to
some range other than the standard 0 - 10 VDC.

Possible Control Modes

0 = Not Configured
1 = Direct Acting Floating Point
2 = Reverse Acting Floating Point
3 = Direct Acting PID
4 = Reverse Acting PID
5 = Relief Pressure Control
6 = Duct Static Pressure Control