Orion Car Audio OE331-21 manual Relay Output #5 Programming Used for Boiler #4

Models: OE331-21

1 42
Download 42 pages 33.78 Kb
Page 32
Image 32

Relay Output #5 Programming ( Used for Boiler #4 )

The fourth boiler stage is enabled to operate if the water temperature is below 150°F and will remain on until it rises to 170°F. The fourth stage can only operate if the third boiler stage relay #4 has been active for at least 5 minutes. Once activated, this stage must remain on for 5 minutes and once de-activated it must remain off for 10 minutes.

The Starting Delay Period that was set for stages 2 to 4 prevent all four boiler stages from activating at the same time as soon as they are enabled to begin operation. Each stage must run for 5 minutes before the next stage can be activated.

Analog Output Programming

Control Source

Not Configured

Since no analog output control is required, simply leave the Control Source set to Not Configured on both outputs and no analog output control will take place.

26

Page 32
Image 32
Orion Car Audio OE331-21 manual Relay Output #5 Programming Used for Boiler #4