15.3.Error Codes Table

Diagnosis

Abnormality /

Abnormality

Protection

Problem

Check location

display

Protection control

Judgement

operation

 

 

 

 

 

 

 

 

H00

No memory of failure

Normal operation

 

 

 

 

 

 

H11

Indoor/outdoor

After operation for

Indoor fan only

Indoor/outdoor

• Indoor/outdoor wire terminal

 

abnormal

1 minute

operation can

communication not establish

• Indoor/outdoor PCB

 

communication

 

start by entering

 

• Indoor/outdoor connection wire

 

 

 

into force cooling

 

 

 

 

 

operation

 

 

 

 

 

 

 

 

H14

Indoor intake air

Continuous for 5s

Indoor intake air temperature

• Indoor intake air temperature

 

temperature sensor

 

 

sensor open or short circuit

sensor lead wire and connector

 

abnormality

 

 

 

 

 

 

 

 

 

 

H15

Compressor

Continuous for 5s

Compressor temperature

• Compressor temperature sensor

 

temperature sensor

 

 

sensor open or short circuit

lead wire and connector

 

abnormality

 

 

 

 

 

 

 

 

 

 

H16

Outdoor current

Current transformer faulty or

• Outdoor PCB faulty or

 

transformer (CT)

 

 

compressor faulty

compressor faulty

 

abnormality

 

 

 

 

 

 

 

 

 

 

H19

Indoor fan motor

Continuous

Indoor fan motor lock or

• Fan motor lead wire and

 

merchanism lock

happen for 7 times

 

feedback abnormal

connector

 

 

 

 

 

• Fan motor lock or block

 

 

 

 

 

 

H23

Indoor heat exchanger

Continuous for 5s

Indoor heat exchanger

• Indoor heat exchanger

 

temperature sensor

 

 

temperature sensor open or

temperature sensor lead wire and

 

abnormality

 

 

short circuit

connector

 

 

 

 

 

 

H27

Outdoor air temperature

Continuous for 5s

Outdoor air temperature

• Outdoor air temperature sensor

 

sensor abnormality

 

 

sensor open or short circuit

lead wire and connector

 

 

 

 

 

 

H28

Outdoor heat exchanger

Continuous for 5s

Outdoor heat exchanger

• Outdoor heat exchanger

 

temperature sensor 1

 

 

temperature sensor 1 open

temperature sensor 1 lead wire

 

abnormality

 

 

or short circuit

and connector

 

 

 

 

 

 

H30

Outdoor discharge pipe

Continuous for 5s

Outdoor discharge pipe

• Outdoor discharge pipe

 

temperature sensor

 

 

temperature sensor open or

temperature sensor lead wire and

 

abnormality

 

 

short circuit

connector

 

 

 

 

 

 

H33

Indoor / outdoor

Indoor and outdoor rated

• Indoor and outdoor units check

 

misconnection

 

 

voltage different

 

 

abnormality

 

 

 

 

 

 

 

 

 

 

H38

Indoor/Outdoor

Brand code not match

• Check indoor unit and outdoor

 

mismatch (brand code)

 

 

 

unit.

 

 

 

 

 

 

H97

Outdoor fan motor

2 times happen

Outdoor fan motor lock or

• Outdoor fan motor lead wire and

 

mechanism lock

within 30 minutes

 

feedback abnormal

connector

 

 

 

 

 

• Fan motor lock or block

 

 

 

 

 

 

H98

Indoor high pressure

Indoor high pressure

• Check indoor heat exchanger

 

protection

 

 

protection (Heating)

• Air filter dirty

 

 

 

 

 

• Air circulation short circuit

 

 

 

 

 

 

H99

Indoor operating unit

Indoor freeze protection

• Check indoor heat exchanger

 

freeze protection

 

 

(Cooling)

• Air filter dirty

 

 

 

 

 

• Air circulation short circuit

 

 

 

 

 

 

F11

4-way valve switching

4 times happen

4-way valve switching

4-way valve

 

abnormality

within 30 minutes

 

abnormal

• Lead wire and connector.

 

 

 

 

 

 

F90

Power factor correction

4 times happen

Power factor correction

• Outdoor PCB faulty

 

(PFC) circuit protection

within 10 minutes

 

circuit abnormal

 

 

 

 

 

 

 

F91

Refrigeration cycle

2 times happen

Refrigeration cycle abnormal

• Insufficient refrigerant or valve

 

abnormality

within 20 minutes

 

 

close

 

 

 

 

 

 

F93

Compressor abnormal

4 times happen

Compressor abnormal

• Power transistor module faulty or

 

revolution

within 20 minutes

 

revolution

compressor lock

 

 

 

 

 

 

F95

Outdoor cooling high

4 times happen

Cooling high pressure

• Check refrigeration system

 

pressure protection

within 20 minutes

 

protection

• Outdoor air circuit

 

 

 

 

 

 

F96

Power transistor module

4 times happen

Power transistor module

• PCB faulty

 

overheating protection

within 30 minutes

 

overheat

• Outdoor air circuit (fan motor)

 

 

 

 

 

 

43

Page 43
Image 43