Panasonic FP2SH manual  Analog I/O units, Analog input, Analog output unit FP2-DA4

Models: FP2 FP2SH

1 28
Download 28 pages 58.71 Kb
Page 20
Image 20

XxxxxFP2/FP2SHXxxxxxxx

XxxxxSpecificationsXxxxxxxx

Analog I/O units

1. Analog input

 

Item

FP2-AD8X

 

 

FP2-RTD

FP2-AD8VI

Number of input points

8 channels

 

 

8 channels

8 channels

 

 

±10V

(1/65536)

 

 

±10V

(1/65536)

 

Voltage

1V ± 5V

(1/13107)

 

 

1V to 5V

(1/13107)

 

 

±100mV

(1/65536)

 

 

 

 

Current

 

note1)

 

 

 

±20mA

(1/32768)

 

 

 

 

 

4mA to 20mA

(1/13107)

 

 

S: 0 to +1500°C

(0.1°C)

 

 

 

 

 

 

 

J: -200 to +750°C

(0.1°C)

 

 

 

 

 

 

 

J: -100 to +400°C

(0.1°C)

 

 

 

 

 

Input range

Thermocouple

K: -200 to +1200°C (0.1°C)

 

 

 

 

 

K: -200 to +1000°C (0.1°C)

 

 

 

 

(resolution)

 

 

 

 

 

 

K: -200 to +600°C

(0.1°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T: -200 to +350°C

(0.1°C)

 

 

 

 

 

 

R: 0 to +1500°C

(0.1°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

N: -200 to +1300°C (0.1°C)

 

 

 

 

 

 

 

 

 

Pt 100 : -200 to +650°C

(0.1°C)

 

 

 

 

 

 

Pt 100 : -100 to +200°C

(0.1°C)

 

 

 

R.T.D

 

 

JPt 100

: -200 to +650°C

(0.1°C)

 

 

 

 

 

 

JPt 100

: -100 to +200°C

(0.1°C)

 

 

 

 

 

 

JPt1000 : -100 to +100°C

(0.1°C)

 

 

 

Voltage

500s/ch (insulated), 5ms (insulated)

 

500s/ch

Conversion

Current

 

 

 

 

500s/ch

speed

Thermocouple

20ms/ch

 

 

 

 

 

R.T.D

20ms/ch

 

 

 

20ms/ch

 

 

 

 

 

 

 

Overall accuracy

Voltage: ±0.1% FS (25 °C) Voltage temperature coefficient: ±0.3% (0 to 55 °C)

 

±0.3% F.S. (0 to 55°C)

±1.0% F.S. (0 to 55°C)

Insulation method

Between the input terminal and FP2 internal circuits: Photocoupler and DC/DC converter

Between the input terminal and FP2 internal circuits: Photocoupler

Between channels: PhotoMOS relay

 

 

 

 

 

 

Digital output

Averaging

Selectable from 3 to 64 times for each channel (Moving average after cutting the maximum and minimum values)

Offset setting

 

 

 

Selectable from K -2048 to +2047 for each channel

 

 

 

 

 

 

Broken wire sensing

Each channel (only when a thermocouple or RTD is inputted)

 

Each channel

 

Input range change method

 

 

 

Batch switching of all channels: By the range setting switch

 

 

 

 

 

Each channels: By shared memory setting

 

 

 

 

 

 

 

 

 

 

Note 1: Current inputs can be converted into voltage inputs by attaching the supplied external resistor to the input terminal section.

2. Analog output

Item

 

Analog output unit FP2-DA4

 

Number of output points

4 channels

 

Output range

 

Voltage

±10V (K-2048 to K+2047)

 

(digital input)

 

Current

0 to 20mA (K0 to K4095)

 

Resolution

 

1/4096

 

Conversion speed

500s/ch

 

Overall accuracy

 

±1.0% F.S. or less (0 to 55°C)

 

Insulation method

– Between the output terminal and FP2 internal circuits: Photocoupler

– Between channels: No insulation

Analog output

 

Hold/Non-hold setting by shared memory setting

20

08/2007

Page 20
Image 20
Panasonic FP2SH manual  Analog I/O units, Analog input, Analog output unit FP2-DA4