PIPING AND CONTROLS
E.TANKLESS HEATER OR COVERPLATE
1.If a tankless coil is used (item 13 or 17), install as pictured. On water boilers, install in opening in front section. On steam boilers, install in opening in rear section. For suggested piping of tankless water heaters refer to Figures 3.6 and 3.7.
Install
above 125°F can cause severe burns instantly or death from scalds.
X1020R and X1082R coils installed in NOTICE
have internal flow controls installed. Do not use external flow controls with these coils.
Figure 3.6: Tankless Coil Piping, Water Boiler
2.If not using a tankless coil, cover the heater opening with cover plate (item 12 or 16).
Be sure rubber gasket is in place NOTICE between cover plate or water heater
plate and boiler section.
3. See Table 3.2 for tankless coil ratings.
Table 3.2: Maximum Tankless Water
Heater Ratings
Heater No. | Capacity* | Boiler Series | |
GPM | |||
|
| ||
|
|
| |
X1020 | 5 | Series EC | |
X1020R | |||
|
| ||
|
|
| |
X1082 | 4 | Series ECT | |
X1082R | |||
|
| ||
|
|
|
*Water Heater ratings are based on intermittent demand
Figure 3.7: Tankless Coil Piping, Steam Boiler
8