BOILER DIMENSIONS & RATINGS
Table 7.1: Boiler Ratings
Series EC/ECT
|
|
| Output5, |
|
|
| AFUE, |
|
| |||
| Input | MBH | Net I=B=R Ratings4 |
| % | Thermal | Combustion | |||||
|
|
|
|
|
|
|
|
|
|
| ||
Model |
|
|
|
| Steam, | Steam, | Water, |
|
|
| Efficiency6, | Efficiency, |
Number | GPH¹ | MBH | Water | Steam | sqft | MBH³ | MBH² | Water | Steam | % | % | |
0.75 | 105 | 92 | 91 | 283 | 68 | 80 | 86.6✸ |
| 85.4✸ | – | – | |
1.00 | 140 | 121 | 120 | 375 | 90 | 105 | 85.3✸ |
| 84.4 | – | – | |
1.20 | 168 | 144 | 142 | 446 | 107 | 125 | 83.9 |
| 82.9 | – | – | |
|
|
|
|
|
|
|
|
|
|
|
|
|
1.25 | 175 | 152 | 151 | 471 | 113 | 132 | 86.1✸ |
| 85.1✸ | – | – | |
1.50 | 210 | 181 | 180 | 563 | 135 | 157 | 85.2✸ |
| 84.5 | – | – | |
1.75 | 245 | 209 | 208 | 650 | 156 | 182 | 84.5 |
| 83.8 | – | – | |
|
|
|
|
|
|
|
|
|
|
|
|
|
1.75 | 245 | 214 | 212 | 663 | 159 | 186 | 86.2✸ |
| 85.6✸ | – | – | |
2.00 | 280 | 241 | 240 | 750 | 180 | 210 | 85.2✸ |
| 84.6 | – | – | |
2.50 | 350 | 286 | 286 | 896 | 215 | 249 | – |
| – | 81.9 | 84.1 | |
2.75 | 385 | 321 | 321 | 1004 | 241 | 279 | – |
| – | 83.3 | 84.4 | |
3.00 | 420 | 347 | 347 | 1083 | 261 | 302 | – |
| – | 82.5 | 83.7 |
Water Content, | Minimum | |
gal | Stack | |
|
| Draft |
|
| Required, |
Water | Steam | in. W.C. |
17.40 | 14.16 | |
|
|
|
17.40 | 14.16 | |
|
|
|
17.40 | 14.16 | |
|
|
|
21.72 | 17.28 | |
|
|
|
21.72 | 17.28 | |
|
|
|
21.72 | 17.28 | |
|
|
|
26.04 | 20.40 | |
|
|
|
26.04 | 20.40 | |
|
|
|
26.04 | 20.40 | |
|
|
|
30.36 | 23.52 | |
|
|
|
30.36 | 23.52 | |
|
|
|
✸As an ENERGY STAR® Partner, PB Heat has determined that these firing rates meet the ENERGY STAR guidelines for energy efficiency. ✝ All chimneys are 8" x 8" x 20' except those models denoted with (✝), which are 8" x 12" x 20'.
1 Burner input based on No. 2 fuel oil with a heating value of 140,000 Btu per gallon.
2 Net I=B=R water ratings based on an allowance of 1.15.
3 Net I=B=R steam ratings based on an allowance of 1.333.
4 Consult factory before selecting a boiler for installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping
systems, etc.
5 Output is Heating Capacity for models with inputs <300 MBH and Gross Output for models with inputs ≥300 MBH. Heating Capacity and Annual Fuel
Utilization Efficiency (AFUE) ratings are based on U.S. Government tests, with 13% CO² and
6 Combustion efficiency and gross output are determined in accordance with The Hydronics Institute’s Testing and rating standard for Heating Boilers; @ 12.5% CO² and
21