PB Heat ECT Series, EC Series Burner Setup & Boiler Operation, 1 Carlin Burner Specifications

Models: ECT Series EC Series

1 27
Download 27 pages 31.96 Kb
Page 18
Image 18
Table 5.1: Carlin Burner Specifications

BURNER SETUP & BOILER OPERATION

Table 5.1: Carlin Burner Specifications

CARLIN BURNER SPECIFICATIONS

Boiler

Firing Rate

Burner

 

Air

Nozzle Size

Pump

Start-up Settings

Head Bar

Model No.

Model No.

 

Shutter

Pressure

Air Band

 

 

 

 

 

 

 

 

 

 

 

 

 

EC/ECT-03-075

.75

EZ-1HP

 

Blank

0.60 70° B DEL³

150 psig

0.55

0.60 - 0.65

 

 

 

 

 

 

 

 

 

EC/ECT-03-100

1.00

EZ-1HP

 

Blank

0.85 70° A DEL

150 psig

0.65

0.85 - 1.00

 

 

 

 

 

 

 

 

 

EC/ECT-03-120

1.20

EZ-1HP

 

Blank

1.00 70° A DEL³

150 psig

0.80

0.85 - 1.00

 

 

 

 

 

 

 

 

 

Boiler

Burner

Air

 

Nozzle Size

Pump

Start-up Settings

Model No.

Model No.

Shutter

Pressure

Head Dim. A

Air Band

 

 

 

 

 

 

 

 

 

EC/ECT-04-125

99FRD

Blank

 

1.00 x 70° B DEL³

150 psig

2

40% open

 

 

 

 

 

 

 

 

EC/ECT-04-150

99FRD

Blank

 

1.25 x 60° B DEL³

150 psig

3

60% open

 

 

 

 

 

 

 

 

EC/ECT-04-175

99FRD

Blank

 

1.50 x 60° B DEL

150 psig

4

100% open

 

 

 

 

 

 

 

 

EC/ECT-05-175

99FRD

Open

 

1.50 x 60° B HAGO³

150 psig

5

10% open

 

 

 

 

 

 

 

 

EC/ECT-05-200

99FRD

Open

 

1.65 x 60° B HAGO

150 psig

5

45% open

 

 

 

 

 

 

 

 

EC/ECT-05-250

99FRD

Open

 

2.00 x 60° B HAGO³

150 psig

8

100% open

 

 

 

 

 

 

 

 

EC/ECT-06-275

102CRD

Open

 

2.25 x 60° B DEL³

150 psig

6

100% open

 

 

 

 

 

 

 

 

EC/ECT-06-300

102CRD

Open

 

2.50 x 60° B DEL

150 psig

8

100% open

 

 

 

 

 

 

 

 

 

Table 5.2: Beckett Burner Specifications

BECKETT BURNER SPECIFICATIONS (140 psig Pump Pressure)

Boiler

Burner

Burner Head

Static Plate

Nozzle Size

Start-up Settings

Head Setting

Model No.

Model No.

Air Shutter

Air Band

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EC/ECT-03-075

AFG-L1¹

L1¹

3-3/8"

0.65

60° B HAGO³

9.0

2

N/A

 

 

 

 

 

 

 

 

 

EC/ECT-03-100

AFG-L1

L1

3-3/8"

0.85

60° B HAGO

10.0

1

N/A

 

 

 

 

 

 

 

 

 

EC/ECT-03-120

AFG-L1

L1

—²

1.00

60° B HAGO³

9.0

2

N/A

 

 

 

 

 

 

 

 

EC/ECT-04-125

AFG-F6

F6

2-3/4"

1.10 80° A DEL³

5.0

1

N/A

 

 

 

 

 

 

 

 

 

EC/ECT-04-150

AFG-F6

F6

2-3/4"

1.25

80° B HAGO

8.0

1

N/A

 

 

 

 

 

 

 

 

 

EC/ECT-04-175

AFG-F6

F6

2-3/4"

1.50

80° B HAGO³

10.0

3

N/A

 

 

 

 

 

 

 

 

 

EC/ECT-05-175

AFG-MV1

M-V1-3

1.50

60° B HAGO³

10.0

3

3

 

 

 

 

 

 

 

 

 

EC/ECT-05-200

AFG-MV1

M-V1-3

1.75

60° B HAGO

10.0

9

3

 

 

 

 

 

 

 

 

 

EC/ECT-05-250

AFG-MV1

M-V1-5

2.00

45° B HAGO³

10.0

5

5

 

 

 

 

 

 

 

 

 

EC/ECT-06-275

CF-375

L1-S

2.25

45° P HAGO³

10.0

6

2

 

 

 

 

 

 

 

 

EC/ECT-06-300

CF-375

L1-S

2.50 45° P HAGO

10.0

6

3

 

 

 

 

 

 

 

 

 

Table 5.3: Riello Burner Specifications

RIELLO BURNER SPECIFICATIONS

Boiler

Firing Rate

Burner

Nozzle Size

Pump Pressure

Start-Up Settings

Model No.

Model No.

Turbulator

Air Damper

 

 

 

 

 

 

 

 

 

 

EC/ECT-03-075

.75

F5

0.60 60° B DEL³

155 psig

0.5

2.1

 

 

 

 

 

 

 

EC/ECT-03-100

1.00

F5

0.85 60° W DEL³

145 psig

2.0

2.6

 

 

 

 

 

 

 

EC/ECT-03-120

1.20

F5

1.00 60° W DEL

145 psig

3.0

2.9

 

 

 

 

 

 

 

EC/ECT-04-125

1.25

F5

1.00 60° W DEL

155 psig

2.5

3.4

 

 

 

 

 

 

 

EC/ECT-04-150

1.50

F10

1.25 60° B DEL³

145 psig

1.5

3.1

 

 

 

 

 

 

 

EC/ECT-04-175

1.75

F10

1.35 60° B DEL

165 psig

2.0

2.5

 

 

 

 

 

 

 

EC/ECT-05-175

1.75

F10

1.35 60° B DEL³

165 psig

2.0

2.5

 

 

 

 

 

 

 

EC/ECT-05-200

2.00

F10

1.50 60° B DEL

170 psig

2.5

2.8

 

 

 

 

 

 

 

EC/ECT-05-250

2.50

F10

2.00 60° B DEL³

155 psig

3.5

4.2

 

 

 

 

 

 

 

EC/ECT-06-275

2.75

F10

2.25 60° B DEL³

150 psig

4.0

4.2

 

 

 

 

 

 

 

EC/ECT-06-300

3.00

F10

2.50 60°B DEL

145 psig

4.5

4.2

 

 

 

 

 

 

 

Factory Installed Nozzles (Packaged Boilers or Burner Cartons) are indicated in Boldface.

1Requires Low Firing Rate Baffle

2Remove Static Plate for 1.20 GPH Rate

3Shipped Loose with Packaged Boiler or Burner Carton

16

Page 18
Image 18
PB Heat ECT Series manual Burner Setup & Boiler Operation, 1 Carlin Burner Specifications, 2 Beckett Burner Specifications