Pentair 100 installation manual Venting, Reduced Maximum Equivalent Vent Run feet

Models: 100

1 40
Download 40 pages 37.49 Kb
Page 30
Image 30
VENTING

VENTING

The vent pipe must be the same size or larger than what is indicated in Table 1. The PowerMax heaters are capable of a 360-degree discharge rotation and operate with a positive vent static pressure and with a vent gas temperature less than 400 F. The total length of the horizontal run must not exceed an equivalent of 45 feet. For all cases, each 90-degree elbow reduces the maximum horizontal vent run by 8 feet and each 45-degree elbow in the vent run reduces the maximum vent run by 4 feet. See Table 2 for the maximum vent lengths using a 90 degree and 45 degree elbows. The PowerMax induced-draft pool and spa heater uses positive pressure to push flue gases through the vent pipe to the outside. This requires a completely sealed vent system--single wall vent pipe with sealed-seams and joints may be used. Flue gases under positive pressure may escape into the dwell- ing with any cracks or loose joints in the vent pipe, or improper vent installation. The vent pipe must be of a sealed-seam construction such as those listed for use with category III appliances. Alternately, single wall or double-wall type B duct which has had duct seams and joints permanently sealed using cements or other suitable means which are rated for use at the flue gas temperatures of 325° F. and are permanent are acceptable. The use of listed thimbles, roof jacks and/or side vent terminals are required; and the proper clearances to combustible materials must be maintained in accordance with type of vent pipe employed- in the absence of a clearance recommendation by the vent pipe manufacturer, the requirements of the Uniform Mechanical Code should be met. The ventilation air and combustion air requirements for the PowerMax heaters are identical to the requirements for the Standard MiniMax heaters of the same output capacities and can be found in the main section of the Operation/Installation Manual, page 18. It is recommended that vent runs over 18 feet be insu- lated to reduce condensation related problems and/or the use of a condensate trap in the vent run close to the heater may be necessary in certain installations such as cold climates. The PowerMax is suitable for through-the- wall venting. (Refer to page A-5, diagram 1.).

Recommended sources for Side-wall vent hood terminals include: The Field Controls Co. (2308 Airport Road, Kingston, NC 28501, (800) 742-8368) and Tjernlund Products Inc. (1601 Ninth Street, White Bear Lake, MN 55110, (800) 255-4208)--consult manufacturer for model information and availability.

Reduced Maximum Equivalent Vent Run (feet)CAUTION

Do NOT combine exhaust vent pipes to a common exhaust vent in multiple unit installations. Run separate vent pipes.

Reduced Maximum Equivalent Vent Run (feet)

 

Additional 90° elbows

Additional 45° elbows

 

after first elbow

after first elbow

 

Quantity

Maximum Length

Quantity

Maximum Length

 

1 (2 total)

37

1 (2 total)

41

 

2 (3 total)

29

2 (3 total)

37

 

3 (4 total)

21

3 (4 total)

33

 

Table 2.

 

 

 

Figure 3.

 

 

 

 

P/N 471048

 

 

A-4

Rev. G 1-22-04

 

 

 

Page 30
Image 30
Pentair 100 installation manual Venting, Reduced Maximum Equivalent Vent Run feet