| 28 |
|
|
NORMAL OPERATION SEQUENCE
(Refer to Figure 21 of Pentair Temperature Controller 7800 keyboard)
The heater features a fully automated firing
Now that the heater has been properly installed and wired for either remote operation or local operation, and you have setup the Pentair Temperature Controller 7800 temperature setpoints as described earlier in manual in Thermostat section, the following is the normal operating sequence when the heater turns on the and the thermostat calls for heat for the pool or spa.
1.The fan will start beginning the heater’s safety prepurging cycle which lasts for 2 minutes. If at anytime during the prepurge cycle the Pentair Temperature Controller 7800 detects that a safety control is not working due to either a safety control malfunction or other unsafe condition the firing sequence will stop until the unsafe condition is removed— “the fault icon related to the problem will illuminate”.
2.After proper completion of the prepurge cycle, the hot surface ignitor (glow coil) will turn on (preheat) for 40 seconds. Once the 40 seconds is passed, the main gas valve will open. At this time, if flame is not safely established and is dectected by the flame sensing curcuit, the ignition module and Pentair Temperature Controller 7800 will shut down and will display an ignition fault and luminate the red service light. Please note that on initial firing of heater when gas supply piping is full of air or after long period of
Insufficient waterflow (pump icon displays), excessive water temperature (high limit icon) cause a
The other category of fault conditions lead to a “hard lockout” of the firing sequence which require a qualified service person to correct before the heater is returned to service. In “hard lockout” the heater must be manually reset (by toggling power to Pentair Temperature Controller 7800) after correction of the fault condition.
Examples of causes of “hard lockouts” include inadequate gas supply pressure and/or failure of fan or fan pressure switches, which all appear as air/gas pressure faults illuminating “blower fan” fault icon and RED “service required” LED.
P/N 471593 | Rev. C |