HARMONIC DISTORTION

What’s the Harm in Harmonics?

This is a variety of harmonic frequencies superimposed on the desirable sine wave frequency passed back along the local power grid to other equipment throughout an entire office building

or local neighborhood. The effect is measured by % VTHD, a measure of the amount of voltage variation within the waveform.

A Powerware Series 9 UPS is the best way to protect critical computer equipment from all potentially harmful power problems.

A concise report on the effects of harmonic distortion on computers

1.The adverse effects of harmonics on electrical power systems are well known. International standards exist to help manage the injection of harmonic currents into the power system.

2.A pure sine wave consists of a single fundamental frequency. Most waves are complex and can be broken down into a series of harmonics. For instance, the 3rd harmonic of the fundamental frequency 60 Hz is 180 Hz. The opposite end of the scale from a pure sine wave is a square wave, which contains all the odd harmonics of a fundamental frequency starting with the 3rd harmonic and extending to infinity.

3.Harmonic distortion is a measure of the ratio between the fundamental and the harmonics that are present in a wave-shape.

4.Distortion is caused by non-linear loads drawing non-sinusoidal currents.

5.Non-linear loads include such office equipment as computers (draw 3rd and 5th harmonics); lighting (ballasts produce 3rd and 5th), transformers (3rd component), power converters (variable speed drives, UPS, electronic ballasts produce 3rd, 5th, 7th, and 11th), and commercial appliances such as photocopiers and printers.

6.The harmonic currents in a distribution system have the following undesirable effects:

a.Significant effects on the performance of computer power supplies.

b.Heating of magnetic devices, which can cause premature insulation failure and breakdown.

c.Triple harmonics produce higher than expected neutral currents, potentially resulting in insulation damage and breakdown due to temperature rise.

d.High neutral currents cause additional voltage drops, reducing available voltage and introducing even more distortion at the load. The resulting neutral-to-ground voltage also causes parasitic ground currents.

e.Additional losses resulting in higher energy costs.

f.Failure of power factor correction capacitors or increased resonance that leads to an even higher order of distortion.

g.High frequency fields that can introduce buzz into telephone lines and corrupt data in adjacent data lines.

h.Stray magnetic fields can introduce annoying interference patterns in VDTs.

i.Undesirable ground currents may cause upstream GFI (ground fault interrupter) to trip, degrading power availability.

Computer loads

Computer power supplies are usually designed to operate over a range of AC input voltages. They produce a DC voltage that is affected by the wave shape of the AC waveform. Harmonic distortion has the effect of actually reducing the computer power supply’s operating voltage.

That variation is compounded by the normal variation of 10%. The end result is that the computer supply may malfunction, hiccup, or fail to provide the required output logic voltages, resulting in potential bit errors. A further negative side-effect of effectively lowering the computer’s operating voltage range is the reduction of hold-up time, essential for the ability of the power supply to ride through power sags (caused by other equipments’ startups). The result is more potential bit errors. The simple fact is that the harmonic distortion prevalent in the modern office has a direct pathway to your computer power supplies, and once there it can cause data loss and other operating errors.

 EATON CORPORATION Reference Guide & Price Book

Page 10
Image 10
Powerware 1500 VA - 60kVa manual Harmonic Distortion, What’s the Harm in Harmonics?, Computer loads

1500 VA - 60kVa specifications

The Powerware 1500 VA - 60 kVA is a robust uninterruptible power supply (UPS) solution designed to provide reliable power protection for critical applications across various environments. With a power range that spans from 1.5 kVA to 60 kVA, this UPS is capable of catering to the diverse needs of modern businesses and organizations, ensuring uninterrupted operations even in the face of power disturbances.

One of the main features of the Powerware 1500 VA - 60 kVA is its advanced double-conversion technology. This technology allows for continuous power conditioning, ensuring that the output power is always clean and stable. By converting incoming AC power to DC and then back to AC, the UPS eliminates voltage fluctuations and protects sensitive electronic equipment from surges, sags, and other electrical anomalies.

The system is equipped with various connectivity options, including USB and serial communication ports, which facilitate easy monitoring and management of power settings. With user-friendly interfaces, operators can quickly access vital information about the UPS’s performance, battery status, and load levels. Additionally, options for network management cards allow for remote monitoring, which is essential for data centers or facilities that require constant oversight of their power systems.

Another notable characteristic of the Powerware 1500 VA - 60 kVA is its scalability. Users can seamlessly expand the UPS capacity by adding additional power modules, making it a future-proof investment that can grow alongside the organization. This feature is particularly valuable for businesses anticipating growth or increased power demands in the future.

The Energy Saver System (ESS) technology integrated into the Powerware series helps to optimize energy efficiency, reducing operating costs while maintaining high performance. By using smart algorithms to minimize losses, the UPS can operate in eco-friendly modes without compromising reliability.

Furthermore, the Powerware UPS units are designed with high availability in mind, featuring hot-swappable batteries and modular designs that allow for easy maintenance without interrupting the power supply. This high-reliability design ensures that operations remain consistent and that downtime is minimized.

Overall, the Powerware 1500 VA - 60 kVA UPS is an exceptional choice for businesses seeking a dependable power protection solution. With its advanced technologies, scalability, and energy efficiency features, it meets the demands of critical applications while delivering consistent performance and reliability.