Specifications

Table 5. Electrical Output

 

120V Models

230V Models

 

 

Power Levels (rated at

500 VA, 320W

nominal inputs)

750 VA, 500W

 

1000 VA, 670W

 

1400 VA, 950W

Power Factor

500 VA, 0.64

 

750–1400 VA, 0.67

Regulation (Normal mode)

-10% to +6% of nominal voltage

Regulation (Battery mode),

Same as selected nominal input voltage

Same as selected nominal input voltage

Nominal Voltage ±5%

110, 120V

220, 230, 240V

Voltage Waveform

Sine wave

Overcurrent Protection

Inverter saturation current limited

Output Receptacles

500–750 VA: (4) 5-15

500–750 VA: (4) 10A, IEC-320

 

1000–1400 VA: (6) 5-15

1000–1400 VA: (6) 10A, IEC-320

 

 

 

Table 6. Environmental and Safety

 

120V Models

230V Models

 

 

Operating Temperature

Up to 1,500 meters: 0°C to 40°C (32°F to 104°F); UL tested 25°C (77°F)

 

Above 1,500 meters: 0°C to 35°C (32°F to 95°F)

Transit/Storage

-15°C to 55°C (5°F to 131°F)

Temperature

 

 

Relative Humidity

5–95% noncondensing

Operating Altitude

Up to 3,000 meters above sea level

Audible Noise

Less than 45 dBA typical

Surge Suppression

ANSI C62.41 Category A (formerly IEEE 587)

Safety Conformance

UL 1778; UL 497A;

UL 1778, UL 497A (data line only);

 

CAN/CSA C22.2, No. 107.1

CAN/CSA C22.2, No. 107.1;

 

 

EN 50091-1-1 and IEC 60950

Safety Markings

UL, cUL

UL, cUL, CE, TUV, C-Tick

EMC (Class B)

FCC Part 15, ICES-003

EN 50091-2, FCC Part 15, ICES-003

 

 

 

24