Specifications
Table 7. Battery
Configuration | 500 VA: (1) 12V, 9 Ah internal battery |
| 750 VA: (2) 12V, 7.2 Ah internal batteries |
| 1000 VA: (2) 12V, 9 Ah internal batteries |
| 1400 VA: (3) 12V, 9 Ah internal batteries |
Voltage | 500 VA: 12 Vdc |
| |
| 1400 VA: 36 Vdc |
Type | Sealed, |
Charging | Advanced charging for faster recovery; less than 3 hours to 90% usable capacity at nominal |
| line and no supplementary power supply load |
Monitoring | Advanced monitoring for earlier failure detection and warning |
|
|
Table 8. Battery Run Times (in Minutes)
|
|
| UPS Models by VA Ratings |
| |
|
|
|
|
|
|
Load (VA) | Watts | 500 | 750 | 1000 | 1400 |
|
|
|
|
|
|
200 | 128 | 17 | 38 | 41 | 58 |
|
|
|
|
|
|
300 | 192 | 11 | 27 | 28 | 41 |
|
|
|
|
|
|
500 | 320 | 5 | 14 | 15 | 28 |
|
|
|
|
|
|
600 | 402 |
| 9 | 10 | 19 |
750 | 503 |
| 6 | 8 | 14 |
900 | 603 |
|
| 6 | 10 |
1000 | 670 |
|
| 5 | 8 |
1200 | 804 |
|
|
| 6 |
1400 | 938 |
|
|
| 5 |
|
|
|
|
|
|
NOTE Battery times are approximate and may vary depending on the load configuration and battery charge.
Powerware® 5115 User’s Guide S www.powerware.com | 25 |