Configuration
C A U T I O N
DO NOT press the Off button while the UPS is in Configuration mode; pressing
the Off button removes all power to your equipment.
1. | Press and hold the On | button and the | button | ||
| simultaneously for one beep. The UPS switches to | ||||
| Configuration mode. |
| |||
2. | Press the On |
| button to scroll through the options. Each time | ||
| |||||
| you press the button, the UPS beeps. The LED for the selected | ||||
| option blinks (see Figure 14 and Table 1). |
|
If you press the On button and nothing happens, the UPS is still in Operation mode. Repeat Step 1 for one beep ONLY to enter Configuration mode, and then perform Step 2.
3.Press the button ONCE to toggle the selected option on or off. The Power On indicator corresponds with the current setting.
Repeat Steps 2 and 3 for each option.
4. Press the On button and the | button simultaneously to |
return to Operation mode at any time. Scrolling past the last LED also returns the UPS to Operation mode.
Power On Indicator
2
Press the On button
to scroll to the next option.
3
Press the Test/Alarm Reset
button to toggle an option on or off.
LEDs
1& 4
Press the On and Test/Alarm Reset buttons simultaneously to toggle between Configuration and Operation mode.
Figure 14. Using the Configuration Mode
16 | Powerware® 5119 User’s Guide : www.powerware.com |