Additional UPS Features
Pin OutAs shown in Table 2, Pins 1 and 2 operate in two modes: Basic Alarms mode and Serial Data mode. Basic Alarms mode has AC fail alarm and output shutdown. Serial Data mode is UPS Code II compliant.
The system always starts in Basic Alarms mode. When serial data is received at Pin 1, the function of Pin 1 and Pin 2 changes to Serial Data mode.
If serial data has not been received before going to battery power, serial communication is disabled until AC input power returns.
6 7 8 9
| 1 | 2 | 3 | 4 | 5 |
|
| Figure 17. Communication Port | |||||
Table 2. Communication Port Configuration |
|
|
|
|
| |
|
|
|
|
|
|
|
Pin | Signal Type |
|
|
|
| Function |
|
|
|
| |||
1 | Basic Alarms Mode - Input: |
| Remote UPS off. In absence of AC power, output is | |||
| 4 to 5 seconds |
|
|
|
| turned off until normal AC power returns |
|
|
|
|
|
|
|
| Serial Data Mode - Input: |
|
|
|
| |
|
|
|
|
|
| 8 bits, No parity, 1 stop bit, 1 start bit |
|
|
|
|
| ||
2 | Basic Alarms Mode - Output: |
|
| AC Input failure | ||
|
|
|
|
|
|
|
| Serial Data Mode - Output: |
|
|
|
| |
|
|
|
|
|
| 8 bits, No parity, 1 stop bit, 1 start bit |
|
|
|
| |||
3 | Output: Open collector transistor ON, 50 mA, 40 Vdc rating |
| AC Input failure | |||
|
|
|
|
|
|
|
4 | Signal Common |
|
|
|
| Signal Common |
|
|
|
| |||
5 | Output: Open collector transistor ON, 50 mA, 40 Vdc rating |
| Impending low battery | |||
|
|
|
|
|
|
|
6 | Input: |
|
|
|
| |
|
|
|
|
|
| when pin changes from +12V to |
|
|
|
|
|
|
|
7 | Input: Relay contact or |
|
|
|
| Remote Emergency |
|
|
|
|
|
| be kept off with low signal or closing relay contact |
|
|
| ||||
8 | Output: 8 to 25 Vdc, 5W constant power (0.63A max. @ 8V) | Auxiliary Control Power | ||||
|
|
|
|
|
|
|
9 | Chassis |
|
|
|
| Connection to chassis |
|
|
|
|
|
|
|