Configuration

Table 1. Configuration Mode LEDs and Options

LED

Option

Power On

Explanation

 

 

Indicator

 

 

120/230V Nominal

ON (default)

Nominal input voltage on low voltage models is 120V and on high voltage

 

Input Voltage

 

models is 230V; all other nominal input voltages are disabled.

 

 

OFF*

120/230V is disabled; one of the other input voltage options is selected.

 

 

 

*This is the default for models that are factory-configured for 100V or 208V (see

 

 

 

the rating on the UPS rear panel).

 

110/220V Nominal

ON

Selecting this option changes the nominal input voltage on low voltage models

 

Input Voltage

 

to 110V and to 220V for high voltage models.

 

 

OFF (default)

110/220V is disabled; one of the other input voltage options is selected.

 

127/240V Nominal

ON

Selecting this option changes the nominal input voltage on low voltage models

 

Input Voltage

 

to 127V and to 240V for high voltage models.

 

 

OFF (default)

127/240V is disabled; one of the other input voltage options is selected.

 

120/230V Extended

ON

The UPS accepts an input voltage within -35% to +20% of 120V or 230V

 

Voltage Mode

 

nominal input voltage before switching to battery.

 

 

OFF (default)

The UPS accepts an input voltage within -30% to +20% of 120V or 230V

 

 

 

nominal input voltage before switching to battery.

 

Site Wiring Fault

ON (default)

Alarm sounds when the polarity of the outlet is reversed or the ground

 

Alarm

 

connection is missing; have a qualified electrician repair the outlet wiring.

 

 

OFF*

Alarm DOES NOT sound when the polarity of the outlet is reversed or the ground

 

 

 

connection is missing.

 

 

 

*Site Wiring Fault is not available for 100V or 208V models; OFF is the default.

 

Low Battery Alarm

ON (default)

Alarm sounds approximately 3 minutes before battery shutdown.

 

 

OFF

Alarm sounds approximately 5 minutes before battery shutdown.

Powerware® 5119 User’s Guide : www.powerware.com