Configuration
Table 1. Configuration Mode LEDs and Options
LED | Option | Power On | Explanation |
|
| Indicator |
|
| 120/230V Nominal | ON (default) | Nominal input voltage on low voltage models is 120V and on high voltage |
| Input Voltage |
| models is 230V; all other nominal input voltages are disabled. |
|
| OFF* | 120/230V is disabled; one of the other input voltage options is selected. |
|
|
| *This is the default for models that are |
|
|
| the rating on the UPS rear panel). |
| 110/220V Nominal | ON | Selecting this option changes the nominal input voltage on low voltage models |
| Input Voltage |
| to 110V and to 220V for high voltage models. |
|
| OFF (default) | 110/220V is disabled; one of the other input voltage options is selected. |
| 127/240V Nominal | ON | Selecting this option changes the nominal input voltage on low voltage models |
| Input Voltage |
| to 127V and to 240V for high voltage models. |
|
| OFF (default) | 127/240V is disabled; one of the other input voltage options is selected. |
| 120/230V Extended | ON | The UPS accepts an input voltage within |
| Voltage Mode |
| nominal input voltage before switching to battery. |
|
| OFF (default) | The UPS accepts an input voltage within |
|
|
| nominal input voltage before switching to battery. |
| Site Wiring Fault | ON (default) | Alarm sounds when the polarity of the outlet is reversed or the ground |
| Alarm |
| connection is missing; have a qualified electrician repair the outlet wiring. |
|
| OFF* | Alarm DOES NOT sound when the polarity of the outlet is reversed or the ground |
|
|
| connection is missing. |
|
|
| *Site Wiring Fault is not available for 100V or 208V models; OFF is the default. |
| Low Battery Alarm | ON (default) | Alarm sounds approximately 3 minutes before battery shutdown. |
|
| OFF | Alarm sounds approximately 5 minutes before battery shutdown. |