Configuration

LED

Option

Power On

Explanation

 

 

Indicator

 

 

Shutdown Delay

ON (default)

5-second delay before unconditional shutdown after the UPS receives a signal

 

 

 

from a computer via the communication port.

 

 

OFF

180-second delay before unconditional shutdown after the UPS receives a signal

 

 

 

from a computer via the communication port. When this LED is not enabled, the

 

 

 

user can also create a new delay time by reconfiguring the communication port.

 

 

 

See “Communication Port Configurations” on page 25 for more information.

 

AC Input Failure

ON (default)

Alarm sounds when there is an AC input failure.

 

 

OFF

Alarm DOES NOT sound when there is an AC input failure.

 

Sleep Mode

ON (default)

When the UPS is on battery and the load is drawing less than 5% of the current,

 

 

 

the UPS shuts down the load. This feature conserves battery power.

 

 

OFF

Select this option if you want a load less than 5% of the current to be protected

 

 

 

by battery power.

 

100/208V Nominal

ON*

Selecting this option changes the nominal input voltage on low voltage models

 

Input Voltage

 

to 100V and to 208V on high voltage models.

 

 

 

*This is the default for factory-configured 100V or 208V models (see the rating

 

 

 

label on the UPS rear panel).

 

 

OFF (default)

100/208V is disabled; one of the other input voltage options is selected.

 

100/208V Extended

ON

Select this option to extend the input voltage within -25% to +25% of 100V or

 

Voltage Mode

 

208V nominal input voltage before switching to battery (available on units that

 

 

 

were specifically ordered with this option).

 

 

OFF (default)

The UPS accepts an input voltage within -20% to +20% of 100V or 208V

 

 

 

nominal input voltage before switching to battery.

 

Reset Defaults

ON (default)

All factory-set defaults are active.

 

 

OFF

One or more factory-set defaults have been changed.

18

Powerware® 5119 User’s Guide : www.powerware.com