Specifications

Table 7. Environmental and Safety

Operating Temperature

Storage Temperature

Relative Humidity

Operating Altitude

Audible Noise

Surge Suppression

Safety Conformance

Safety Markings

EMC

120V Models

230V Models

0°C to 40°C (32°F to 104°F); UL tested 25°C (77°F)

-20°C to 60°C (-4°F to 140°F)

5-95% noncondensing

Up to 3,000 meters above sea level

Less than 45 dBA typical

IEEE 587/ANSI C62.41 Category B

UL 1778; CAN/CSA C22.2, No. 107.1

UL 1778; CAN/CSA C22.2, No. 107.1;

 

EN 50091-1 and IEC 60950

 

 

UL, CSA

UL, CSA, CE

 

 

FCC, VCCI

EN 50091-2

 

 

Table 8. Indicators and Controls

Serial Communication

Interface

Contact Closures

Intelligent serial communication to provide alarms with history, measured parameters, self-test, and many other features; contact your authorized dealer for UPS/computer communication software options

Ergonomic Indicators: Wiring Fault, Battery Service, Communication, Operation, System Normal

Bar Graphs: Input Level, Battery Charge Level, % Load

AC Input Failure, Low Battery

Table 9. Battery

Configuration

Voltage

Type

Charging

Monitoring

120V Models

230V Models

 

 

1000-1500 VA: internal batteries

1000-1500 VA: internal batteries

2000-3000 VA: external PW5119 1048BP

2000-3000 VA: external PW5119 1748BP

 

 

24 Vdc for internal; 48 Vdc for external

 

 

 

Sealed, maintenance-free, valve-regulated, lead-acid

Advanced charging for faster recovery; approximately 4 hours to 90% usable capacity at nominal line and no supplementary power supply load

Advanced monitoring for earlier failure detection and warning

Powerware® 5119 User’s Guide : www.powerware.com

31