QHT Boiler manual Installation considerations, 3Wood

Models: Boiler

1 40
Download 40 pages 34.95 Kb
Page 15
Image 15
Installation considerations

Installation considerations

When the 3WOOD is installed, check that The flue, if reused:

Supplies the negative pressure required for the new boiler (see the table of technical specifications on page 10);

is suitable for the temperature of the products of combustion, and has been calculated and constructed according to the required standards; recommended by NFPA

is as straight as possible, airtight, insulated and is not blocked or choked;

is fitted with a cleanout door

The heating system should be flushed, cleaned of any slime and deposits, vented and tested for water tightness.

The heating system should be equipped with a new expansion tank of sufficient size to handle the volume of both boilers.

The 3WOOD Boiler should be equipped with its own make-up water.

Model #

Min. Output

 

(BTU/HR)

3Wood 5

89,000

3Wood 6

104,000

3Wood 7

120,000

FIREBOX

Width

Height

DEPTH

(inches)

(inches)

16.5”

 

 

20”

24”

38”

23.5”

 

 

 

 

1 1/2”

 

1 1/2”

 

 

 

Length

WATER

Draft

Weight

(inches)

CONTENT

(inch)

(LBS)

(US-GALLONS)

25

11

.07

695

30

12.5

.10

804

34

14

.12

903

15