CLEARANCES TO COMBUSTIBLES (UL AND ULC)

FLOOR PROTECTION: Floor protector must be noncombustible material or equivalent, extending beneath heater and to the front/ sides/rear as indicated.

NOTE: A 3/8” (10mm) minimum thickness tile or equivalent is recommended, but not required.

Minimum clearances to Combustible Materials (in inches and millimeters) for Quadra-Fire 3100 Standard Stove

 

 

Chimney &

 

 

 

 

 

 

Installation

Clearance

Connector

A

B

C

D

E

F

Residential

Standard

Note 1

14”(356)

26”(661)

18”(457)

12”(305)

18”(457)

10”(254)

Residential/Mobile Home

Reduced

Note 2

12”(305)

26”(661)

16”(406)

10”(254)

18”(457)

8”(203)

Alcove

Standard

Note 2 & 3

12”(305)

26”(661)

N/A

10”(254)

18”(457)

8”(203)

Minimum clearances to Combustible Materials (in inches and millimeters) for Quadra-Fire 3100 with top shield

 

 

 

Chimney &

 

 

 

 

 

 

Installation

Clearance

Connector

A

B

C

D

E

F

Residential

Standard

Note 1

12”(305)

24”(610)

16”(406)

10”(254)

16”(406)

8”(203)

Residential/Mobile Home

Reduced

Note 2

10”(254)

24”(610)

14”(356)

8”(203)

16”(406)

6”(153)

Alcove

Standard

Note 2 & 3

10”(254)

24”(610)

N/A

8”(203)

16”(406)

6”(153)

Minimum clearances to Combustible Materials (in inches and millimeters) for Quadra-Fire 3100 Step Top Stove

 

 

 

Chimney &

 

 

 

 

 

 

Installation

Clearances

Connector

A

B

C

D

E

F

Residential

Standard

Note 1

12”(305)

24”(610)

16”(406)

10”(254)

16”(406)

8”(203)

Residential/Mobile Home

Reduced

Note 2

10”(254)

24”(610)

14”(356)

8”(203)

16”(406)

6”(153)

Alcove

Standard

Note 2 & 3

10”(254)

24”(610)

N/A

8”(203)

16”(406)

6”(153)

Note 1: 6” (152mm) diameter single wall, minimum 24 MSG black or blued steel connector pipe with a listed factory-built type HT chimney suitable for use with solid fuels or a masonry chimney.

Note 2: 6” (152mm) diameter double wall insulated connector pipe with listed factory-built type HT chimney or a masonry chimney. (Mobile home venting system must be equipped with a rain cap and spark arrestor.) For installations with a preexisting class A chimney system, a listed stainless steel chimney liner should be installed, or the existing chimney examined by a chimney sweep for acceptable further use.

Note 3: Alcove specifications: Maximum depth of alcove shall be no more than 48” (1219mm). For additional alcove information and clearances, refer to clearances to combustibles above.

NOTE: Unit is approved for use with listed double wall air-insulated chimney connector or elbows.

When locating your stove consider safety, convenience, traffic flow, and the fact that the stove will need a chimney and chimney connector.

FLOOR PROTECTION: Floor protector must be noncombustible material, extending beneath heater and to the front/sides/rear as indicated.

NOTE: A 3/8” (10mm) minimum thickness tile or equivalent is recommended, but not required.

NFPA 211: Use a noncombustible material with 1” (25mm) ventilated air space to reduce clearances. However, this is not to exceed 50% of Quadra-Fire’s specified clearances.

NOTE: Must follow NFPA 211 spacing and materials to qualify. It is also subject to local jurisdiction.

AVOID FIRE: Maintain the designated clearances to combustibles. Insulation must not touch the chimney. You must maintain the designated air space clearance around the chimney. This space around a chimney is necessary to allow natural heat removal from the area. Insulation in this space will cause a heat buildup, which may ignite wood framing.