CLEARANCES TO COMBUSTIBLES (UL AND ULC)
FLOOR PROTECTION: Floor protector must be noncombustible material or equivalent, extending beneath heater and to the front/ sides/rear as indicated.
NOTE: A 3/8” (10mm) minimum thickness tile or equivalent is recommended, but not required.
Minimum clearances to Combustible Materials (in inches and millimeters) for
|
| Chimney & |
|
|
|
|
|
|
Installation | Clearance | Connector | A | B | C | D | E | F |
Residential | Standard | Note 1 | 14”(356) | 26”(661) | 18”(457) | 12”(305) | 18”(457) | 10”(254) |
Residential/Mobile Home | Reduced | Note 2 | 12”(305) | 26”(661) | 16”(406) | 10”(254) | 18”(457) | 8”(203) |
Alcove | Standard | Note 2 & 3 | 12”(305) | 26”(661) | N/A | 10”(254) | 18”(457) | 8”(203) |
Minimum clearances to Combustible Materials (in inches and millimeters) for |
| |||||||
|
| Chimney & |
|
|
|
|
|
|
Installation | Clearance | Connector | A | B | C | D | E | F |
Residential | Standard | Note 1 | 12”(305) | 24”(610) | 16”(406) | 10”(254) | 16”(406) | 8”(203) |
Residential/Mobile Home | Reduced | Note 2 | 10”(254) | 24”(610) | 14”(356) | 8”(203) | 16”(406) | 6”(153) |
Alcove | Standard | Note 2 & 3 | 10”(254) | 24”(610) | N/A | 8”(203) | 16”(406) | 6”(153) |
Minimum clearances to Combustible Materials (in inches and millimeters) for |
| |||||||
|
| Chimney & |
|
|
|
|
|
|
Installation | Clearances | Connector | A | B | C | D | E | F |
Residential | Standard | Note 1 | 12”(305) | 24”(610) | 16”(406) | 10”(254) | 16”(406) | 8”(203) |
Residential/Mobile Home | Reduced | Note 2 | 10”(254) | 24”(610) | 14”(356) | 8”(203) | 16”(406) | 6”(153) |
Alcove | Standard | Note 2 & 3 | 10”(254) | 24”(610) | N/A | 8”(203) | 16”(406) | 6”(153) |
Note 1: 6” (152mm) diameter single wall, minimum 24 MSG black or blued steel connector pipe with a listed
Note 2: 6” (152mm) diameter double wall insulated connector pipe with listed
Note 3: Alcove specifications: Maximum depth of alcove shall be no more than 48” (1219mm). For additional alcove information and clearances, refer to clearances to combustibles above.
NOTE: Unit is approved for use with listed double wall
When locating your stove consider safety, convenience, traffic flow, and the fact that the stove will need a chimney and chimney connector.
FLOOR PROTECTION: Floor protector must be noncombustible material, extending beneath heater and to the front/sides/rear as indicated.
NOTE: A 3/8” (10mm) minimum thickness tile or equivalent is recommended, but not required.
NFPA 211: Use a noncombustible material with 1” (25mm) ventilated air space to reduce clearances. However, this is not to exceed 50% of
NOTE: Must follow NFPA 211 spacing and materials to qualify. It is also subject to local jurisdiction.
AVOID FIRE: Maintain the designated clearances to combustibles. Insulation must not touch the chimney. You must maintain the designated air space clearance around the chimney. This space around a chimney is necessary to allow natural heat removal from the area. Insulation in this space will cause a heat buildup, which may ignite wood framing.
Page 6