Quadra-Fire 3100 owner manual

Models: 3100

1 32
Download 32 pages 9.09 Kb
Page 9
Image 9
The chimney must have a fire clay flue liner (or equivalent) with a minimum thickness of 5/8” (16mm) and must be installed with refractory mortar. There must be at least ½” (13mm) air space between the flue liner and the chimney wall (Figure 4). An equivalent liner must be a listed chimney liner system or other approved material.

The chimney must have a fire clay flue liner (or equivalent) with a minimum thickness of 5/8” (16mm) and must be installed with refractory mortar. There must be at least ½” (13mm) air space between the flue liner and the chimney wall (Figure 4). An equivalent liner must be a listed chimney liner system or other approved material.

FIGURE 4

A chimney inside the house must have at least 2” (50mm) of clearance to the combustible structure. A chimney outside the house must have at least 1” (25mm) clearance to the combustible structure. Firestops must be installed in the spaces where the chimney passes through floors and/or ceiling (Figure 5).

FIGURE 5