INSTALLATION

MOBILE HOME INSTALLATION

You must use Outside Air Kit 831-1780 for

installation in a mobile home. Use of alternative

material will void your warranty.

1.An outside air inlet must be provided for combustion and must remain clear of leaves, debris, ice and/or snow. It must be unrestricted while unit is in use to prevent room air starvation which can cause smoke spillage and an inability to maintain a fire. Smoke spillage can also set off smoke alarms.

2.Unit must be secured to the mobile home structure by bolting pedestal through hearth pad and into floor.

3.Unit must be grounded with #8 copper grounding wire or equivalent and terminated at each end with N.E.C. approved grounding device.

4.Stove must be installed with an approved UL103 HT ventilated chimney connector, UL103 HT chimney, and terminal cap with spark arrestor. Never use a single wall connector (stove pipe) in a mobile home installation. Use only double-wall connector pipe, Dura-Vent DVL, Selkirk metalbestos DS or Security DL double wall connector.

5.Refer to page 6 of this manual or the Serial Number label on the back of the stove for clearances to combustibles.

6.Floor protections requirements on page 10 must be followed precisely.

7.In Canada, this appliance must be connected to a 6” (152mm) factory-built chimney conforming to CAN/ULC-629M, STANDARD FOR FACTORY BUILT CHIMNEYS. Floor protection referenced on page 10 must be followed, as well as use of Canadian Floor Protector, Part 842-3950 provided with stove.

8.Use silicone to create an effective vapor barrier at the location where the chimney or other component penetrates to the exterior of the structure.

9.Follow the chimney and chimney connector manufacturer’s instructions when installing the flue system for use in a mobile home.

NOTE: Offsets from the vertical, not exceeding 45°, are allowed per Section 905(a) of the Uniform Mechanical Code (UMC). Offsets greater than 45° are considered horizontal and are also allowed, providing the horizontal run does not exceed 75% of the vertical height of the vent. Construction, clearance and termination must be in compliance with the UMC Table 9C. This installation also complies with NFPA 211.

WARNING: NEVER DRAW COMBUSTION AIR FROM A WALL, FLOOR OR CEILING CAVITY OR FROM ANY ENCLOSED SPACE SUCH AS AN ATTIC OR GARAGE.

WARNING: DO NOT INSTALL IN A SLEEPING ROOM.

CAUTION: THE STRUCTURAL INTEG- RITY OF THE MOBILE HOME FLOOR, WALL, AND CEILING/ROOF MUST BE MAINTAINED (i.e., DO NOT CUT THROUGH FLOOR JOIST, WALL STUD, CEILING TRUSS, ETC.)

Spark Arestor Cap

Storm Collar

Roof Flashing

Joist Shield/Firestop

Listed Chimney

Outside Air Kit Connector

Floor Protector

Outside Air Floor Vent

NOTE: Top sections of chimney must be removable to allow maximum clearance of 13.5’ (411cm) from ground level for transportation purposes.

10. Burn wood only. Other types of fuels may generate poisonous gases (e.g., carbon monoxide).

11 If unit burns poorly while house exhaust blower is on in home, increase combustion air to the stove.