Quadra-Fire 5100I-GD-B, 5100I-NL-B warranty Chimney Termination Requirements, Rule

Models: 5100I-GD-B 5100I-NL-B

1 44
Download 44 pages 14.54 Kb
Page 19
Image 19

5100-I ACT WOOD INSERT

R

L. Chimney Termination Requirements

Follow manufacturers instructions for clearances, securing, flashing and terminating the chimney.

Must have an approved and listed cap

Must not be located where it will become plugged by snow or other material

Must terminate at least 3 feet (91cm) above the roof and at least 2 feet (61cm) above any portion of the roof within 10 feet (305cm).

Must be located away from trees or other structures

NOTE:

Chimney performance may vary.

Trees, buildings, roof lines and wind conditions affect performance.

Chimney height may need adjustment if smoking or overdraft occurs.

M. 2-10-3 Rule

These are safety requirements and are not meant to assure proper flue draft

2 ft. (61cm)

10' (305cm) To Nearest Roofline

3 in. (91cm)

Minimum

Less than 10 ft. (305cm)

2 ft. (61cm)

3 ft. (91cm)

 

Minimum

Figure 19.1

Pitched Roof

10 ft. (305cm) or more

Less than 10 ft. (305cm)

 

 

Wall or Parapet

2 ft. (61cm)Minimum

3 ft. (91cm) Minimum

3 ft. (91cm) Minimum

 

Figure 19.2

Flat Roof

April 21, 2010

438-0380E

Page 19

Page 19
Image 19
Quadra-Fire 5100I-GD-B, 5100I-NL-B warranty Chimney Termination Requirements, Rule