D. How to Use the Vent Graph | E. Venting Guidelines |
1.Measure the vertical distance from the center line of the flue pipe to the center of the 90° elbow. On the graph below, draw a horizontal line from that measurement on the vertical axis across until it intersects with the slanted line.
2.From the point of this intersection, draw a vertical line to the bottom of the graph.
3.The point at which this line meets the bottom line of the graph is the maximum length of the horizontal run.
EXAMPLE 1: If the vertical dimension from the center line of the fl ue vent to the center of the 90° elbow is 7 ft. (2m), the horizontal run to the outer wall fl ange must not exceed 9
EXAMPLE 2: If the vertical dimension from the center line of the fl ue vent is 21 ft. (6m), the horizontal run to the outer wall fl ange must not exceed 4
4.Each 90° elbow is equivalent to 3 ft. (914mm) of vent pipe and each 45° elbow is equivalent to 1 ft. (305mm) of vent pipe, and must be subtracted from the vent pipe run. A single horizontal to vertical 90° elbow is already calculated into the allowable 15 ft. (5m) run. Each additional 90° elbow reduces the maximum horizontal distance by 3 ft. (914mm).
EXAMPLE: The use of 3 elbows would reduce the allowable horizontal run to 9 ft. (3
NOTES
The maximum horizontal vent run is 15 ft. (5m) when the vertical vent rise is 10 ft. (3m).
Horizontal sections require a 1/4 in. (6mm) rise for every 12 in. (305mm) of horizontal travel.
Exterior Vent Diameter =
Horizontal sections require noncombustible support every 3 ft. (914mm), e.g. wall straps.
For any vertical termination a minimum of 6 in. (152mm) vertical must be used.
EXCEPTIONS
FOR HORIZONTAL INSTALLATIONS:
The maximum horizontal vent run is 30 in. (762mm).
The maximum horizontal vent run with a 45° elbow is 18 in. (457mm).
No external minimum rise is required.
The minimum horizontal vent run is 6 in. (152mm).
NOTE: If your installation falls within the
*In the Commonwealth of Massachusetts, the word damper shall be replaced with the words flue restrictor.
25 ft. (8m) | 25' |
|
|
|
|
|
|
|
|
Maximum Vertical | 24' |
|
|
|
|
|
|
|
|
Example 2 | 22' |
|
|
|
|
|
|
|
|
| 20' |
|
|
|
|
|
|
|
|
| 18' | Adjust |
|
|
|
|
|
|
|
| 16' | Intake |
|
|
|
|
|
|
|
VERTICAL DISTANCE | Damper |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| ||
14' |
|
|
|
|
|
|
|
| |
FROM APPLIANCE TO |
| Install Flue |
|
|
|
| |||
|
|
|
|
|
| ||||
90° ELBOW | 12' |
|
| Restrictor |
|
|
|
| |
| 10' |
|
|
|
|
|
|
|
|
Example 1 | 8' |
|
|
|
|
|
|
| Termination |
|
|
|
|
|
|
|
| ||
| 6' |
|
|
|
|
|
|
| cap |
|
|
|
|
|
|
|
|
| |
6 ft. (2m) Minimum | 4' |
|
|
|
|
|
|
|
|
Vertical Termination |
|
|
|
|
|
|
|
| |
2' |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |
C |
|
|
|
|
|
|
|
|
|
L |
| 2' | 4' | 6' | 8' | 10' | 12' | 14' | 15' |
|
| ||||||||
|
|
|
| Termination Cap |
|
|
| ||
| 6 in. (152mm) |
| 30 in. (762mm) Maximum Horizontal run with no | ||||||
| Minimum starter pipe | vertical pipe and with 1/4 in. (6mm) rise per foot. | |||||||
Figure 5.2 |
|
|
| Must use approved Termination Cap. |
August 1, 2008 | Page 11 |