Quadra-Fire GARNET-D-PMH, GARNET-MBK D. How to Use the Vent Graph, E. Venting Guidelines

Models: GARNET-D-CSB GARNET-D-CWL GARNET-MBK GARNET-D-MBK GARNET-D-PMH

1 56
Download 56 pages 40.99 Kb
Page 11
Image 11
D. How to Use the Vent Graph

D. How to Use the Vent Graph

E. Venting Guidelines

1.Measure the vertical distance from the center line of the flue pipe to the center of the 90° elbow. On the graph below, draw a horizontal line from that measurement on the vertical axis across until it intersects with the slanted line.

2.From the point of this intersection, draw a vertical line to the bottom of the graph.

3.The point at which this line meets the bottom line of the graph is the maximum length of the horizontal run.

EXAMPLE 1: If the vertical dimension from the center line of the fl ue vent to the center of the 90° elbow is 7 ft. (2m), the horizontal run to the outer wall fl ange must not exceed 9 ft.-8 in. (3m).

EXAMPLE 2: If the vertical dimension from the center line of the fl ue vent is 21 ft. (6m), the horizontal run to the outer wall fl ange must not exceed 4 ft.-3 in. (1m).

4.Each 90° elbow is equivalent to 3 ft. (914mm) of vent pipe and each 45° elbow is equivalent to 1 ft. (305mm) of vent pipe, and must be subtracted from the vent pipe run. A single horizontal to vertical 90° elbow is already calculated into the allowable 15 ft. (5m) run. Each additional 90° elbow reduces the maximum horizontal distance by 3 ft. (914mm).

EXAMPLE: The use of 3 elbows would reduce the allowable horizontal run to 9 ft. (3 -1 = 2 elbows x 3 ft. = 6 ft.; 15 ft. max. - 6 ft. = 9 ft. max.).

NOTES

The maximum horizontal vent run is 15 ft. (5m) when the vertical vent rise is 10 ft. (3m).

Horizontal sections require a 1/4 in. (6mm) rise for every 12 in. (305mm) of horizontal travel.

Exterior Vent Diameter = 6-5/8 in. (168mm); Inner Vent Diameter = 4 in. (102mm)

Horizontal sections require noncombustible support every 3 ft. (914mm), e.g. wall straps.

For any vertical termination a minimum of 6 in. (152mm) vertical must be used.

EXCEPTIONS

FOR HORIZONTAL INSTALLATIONS:

The maximum horizontal vent run is 30 in. (762mm).

The maximum horizontal vent run with a 45° elbow is 18 in. (457mm).

No external minimum rise is required.

The minimum horizontal vent run is 6 in. (152mm).

NOTE: If your installation falls within the gray-shaded area on graph, see information on intake damper operation, on page 36.

*In the Commonwealth of Massachusetts, the word damper shall be replaced with the words flue restrictor.

25 ft. (8m)

25'

 

 

 

 

 

 

 

 

Maximum Vertical

24'

 

 

 

 

 

 

 

 

Example 2

22'

 

 

 

 

 

 

 

 

 

20'

 

 

 

 

 

 

 

 

 

18'

Adjust

 

 

 

 

 

 

 

 

16'

Intake

 

 

 

 

 

 

 

VERTICAL DISTANCE

Damper

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14'

 

 

 

 

 

 

 

 

FROM APPLIANCE TO

 

Install Flue

 

 

 

 

 

 

 

 

 

 

90° ELBOW

12'

 

 

Restrictor

 

 

 

 

 

10'

 

 

 

 

 

 

 

 

Example 1

8'

 

 

 

 

 

 

 

Termination

 

 

 

 

 

 

 

 

 

6'

 

 

 

 

 

 

 

cap

 

 

 

 

 

 

 

 

 

6 ft. (2m) Minimum

4'

 

 

 

 

 

 

 

 

Vertical Termination

 

 

 

 

 

 

 

 

2'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

 

L

 

2'

4'

6'

8'

10'

12'

14'

15'

 

 

 

 

 

 

Termination Cap

 

 

 

 

6 in. (152mm)

 

30 in. (762mm) Maximum Horizontal run with no

 

Minimum starter pipe

vertical pipe and with 1/4 in. (6mm) rise per foot.

Figure 5.2

 

 

 

Must use approved Termination Cap.

August 1, 2008

Quadra-Fire · Garnet-T · 7016-127F

Page 11

Page 11
Image 11
Quadra-Fire GARNET-D-PMH D. How to Use the Vent Graph, E. Venting Guidelines, Exceptions For Horizontal Installations