8 in.

 

(203mm)

 

 

7 in.

 

(178mm)

7 in.

6 in.

(178mm)

 

(152mm)

Figure 5.7

1/4 in. (6mm) Manual background

Fold Strap HereManual background

Sheet Metal Screw

Wall Thimble Cover/Ceiling

Firestop as Required by Local

JurisdictionStrap

Figure 5.9

Wall Thimble

(NOTE: Some termination caps may cause the vent pipe to be off center on the flashing). Ensure that proper clearances to combustible materials are maintained. If you are not using an approved termination cap with a built-in vinyl siding standoff on a building with vinyl siding, a vinyl siding standoff should be installed between the vent cap and the exterior wall (Figure 5.8). Attach the vinyl siding standoff to the horizontal vent termination. The vinyl siding standoff prevents excessive heat from possibly melting the vinyl siding material. Vent terminal shall not be recessed into a wall or siding. Remove siding from the area where the standoff will be located.

Note: The attachment from the vent pipe to the vent termination cap must be sealed with silicone. Termination caps shall not be recessed into a wall or siding.

Manual background WARNING

Fire Hazard.

Exhaust Fume Risk.

Impaired Performance of Appliance.

Ensure vent components are locked together correctly.

Pipe may separate if not properly joined.

WALL THIMBLE COVER

WALL THIMBLE

Figure 5.8

VINYL SIDING

Apply sealant to all four sides

Manual background SCREWS

Manual background Bolt horizontal top to vinyl standoff

Manual backgroundManual backgroundManual backgroundManual background SCREWS

Vinyl siding standoff with siding beneath removed

Manual background WARNING

Do NOT connect a pipe section to a termination cap without using the telescoping fl ue section found on the termination cap.

Manual backgroundWARNING

Burn Risk.

Local codes may require installation of a cap shield to prevent anything or anyone from touching the hot cap.

Step 5.

Place the wall thimble cover over the pipe assembly and slide the appliance and vent assembly towards the wall, carefully inserting the vent pipe into the vent termination cap assembly. It is important that the vent pipe extend into the vent termination cap a sufficient distance so as to result in a minimum pipe overlap of 1-1/4 in. (32mm). Secure the connection between the vent pipe and the vent termination cap by attaching the two sheet metal strips extending from the vent termination cap assembly into the outer wall of the vent pipe. Use the two sheet metal screws provided to connect the strips to the pipe section (Figure 5.9).