GAS SUPPLY CONNECTIONS

GAS SUPPLY CONNECTIONS

Gas piping must have a sediment trap ahead of the heater gas controls, and a manual shut-off valve lo- cated outside the heater jacket. All gas piping should be tested after installation in accordance with local codes.

Manual Shut-Off

Heater Jacket

Gas Valve

Valve

 

 

 

Gas Inlet

Union

 

Sediment Trap

Fig. # 8090.0

CAUTION: The heater and its manual shut off valve must be disconnected from the gas supply during any pressure testing of that system at test pressures in excess of 1/2 psig (3.45 KPA). Dissipate test pressure in the gas supply line before reconnecting the heater and its manual shut off valve to gas supply line.

FAILURE TO FOLLOW THIS PROCEDURE MAY DAMAGE THE GAS VALVE. OVER PRESSURED GAS VALVES ARE NOT COVERED BY WARRANTY. The heater and its gas connections shall be leak tested before placing the appliance in operation. Use soapy water for leak test. Do NOT use open flame.

NOTE: Do not use teflon tape on gas line pipe thread. A flexible sealant is recommended.

A minimum of 7" W.C. and a maximum of 14" W.C. upstream pressure under load, and no load conditions must be provided for natural gas or a minimum of 12" W.C. and a maximum of 14" for propane gas.

GAS PRESSURE REGULATOR

The gas pressure regulator is present and sealed at 4"W.C. for natural gas, and 11"W.C. for propane gas. Between the gas valve and the burners is a 1/8" pipe plug. The pressure at this point , taken with a manometer, should be about 3.7"W.C. natural gas and 10.5"W.C. propane gas. If an adjustment is needed, remove seal and turn adjustment screw clockwise

to increase pressure or counter-clockwise to decrease pressure.

Manometer

Gas Pressure

Test Upstream

Manual Shut

Off Valve

Gas Valve

Gas Pressure Test

at Gas Valve

Gas Pressure Test at Heater

Fig. # 8149.0

ROBERTSHAW VALVE

W. C. adjustment

HONEYWELL VALVE

W. C. adjustment

Fig. # 8081.0

PIPE SIZING FOR GAS CONNECTIONS

MAXIMUM EQUIVALENT PIPE LENGTH

Natural Gas 1000BTU/FT3 .60 Specific Gravity

@ 0.5" WC Pressure Drop

Propane Gas 2500BTU/FT3 1.53 Specific Gravity

@ 0.5" WC Pressure Drop

MODEL

 

 

1/2"

 

3/4"

 

1"

 

 

 

 

 

 

 

 

 

 

 

 

 

N

 

P

N

 

P

N

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

155B

15

 

35

60

 

145

200

 

500

 

 

 

 

 

 

 

 

 

 

 

 

 

14