Raypak 155C installation instructions Venting Connections

Models: 155C

1 35
Download 35 pages 10.56 Kb
Page 12
Image 12
VENTING CONNECTIONS

INDOOR HEATERS

The design is also certified for indoor installation when equipped with the approved draft hood. Locate heater as close as practical to a chimney or gas vent. Heater must always be vented to the outside. See Vent Piping Section for venting details. Minimum allowable space is shown on the nameplate.

INDOOR

Manual background DRAFT HOOD

Fig. # 9305

COMBUSTION AIR (INDOOR UNITS ONLY)

AIR FOR COMBUSTION AND VENTILATION (Indoor Units Only)

The heater must have both combustion and ventilation air. Minimum requirements for net free air supply openings, one 12 inches from ceiling for ventilation and one 12 inches from the floor for combustion air as outlined in Z 223.1 - 1988 and any local codes that may have jurisdiction.

CAUTION: Combustion air must not be contaminated by corrosive chemical fumes which can damage the heater and void the warranty.

a.All Air From Inside the Building:

Each opening shall have a minimum of 151 net free square inches.

b.All Air From Outdoors:

When air is supplied directly from outside of building, each opening shall have a minimum of 38 net free square inches.

VENTING CONNECTIONS

Top Vent Opening

VENT TERMINAL (Outdoor) STACKLESS TOP

STEP 1 : Remove the front (4) screws which fasten jacket top to heater.

STEP 2 : Line up top vent opening over heater vent opening.

STEP 3 : Lower outdoor top onto unit lining up slots in outdoor top with screw holes in jacket top.

STEP 4 : Reinstall (6) screws to secure jacket top and outdoor top to unit.

Fig. # 9306

12

Page 12
Image 12
Raypak 155C installation instructions Venting Connections