START-UPPROCEDURES

START-UPPROCEDURES

SECTION 1. Filling the System

Fill system with water. Purge all air from the system using purge valve sequence. After system is purged of air, lower system pressure.

Flush system before putting into operation to assure that foreign material does not damage pump seals.

SECTION 2. Checking the Circulator

Before lighting the heater and after system is filled, make sure that circulator is operating properly. Manual gas valve should be off.

NOTE: Circulator motor supplied with the heater does not require lubrication.

FOR STANDING PILOT MODEL WITH ROBERTSHAW GAS VALVE, ON/OFF OPERATION

1.STOP! Read the safety information above.

2.Set the tankstat on the lowest setting.

3.Turn OFF all electric power to the heater.

4.Push in gas control knob slightly and turn clockwise to "OFF".

8.Push in control knob all the way and hold in, immediately light the pilot with a match. Continue to hold control knob in for about one minute after the pilot is lighted, release knob and it will pop back up. Pilot should remain lighted. If it goes out, repeat steps 4 through 8.

* If knob does not pop up when released, stop and immediately call your service technician or gas supplier.

* If the pilot does not stay lit after several tries, turn the gas control knob to "OFF" and call your service technician or gas supplier.

9.Stand to the side of the heater and turn the gas control knob counter-clockwise to "ON".

10.Turn "ON" all electrical power to the heater.

11.Set the tankstat to the desired setting.

FOR STANDING PILOT MODEL WITH HONEYWELL GAS VALVE, ON/OFF OPERATION

1.STOP! Read the safety information.

2.Set the tankstat to the lowest setting.

3.Turn Off all electrical power to the heater.

4.Turn gas control knob clockwise to "OFF".

GASCONTROL

KNOBSHOWN

IN"OFF"POSITION

GASINLET

NOTE: Knob cannot be turned from "PILOT" to "OFF" unless knob is pushed in slightly. Do not force.

5.Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If your smell gas, STOP! Follow "B" in the safety information above on this label. If you don't smell gas, go to the next step.

6.Locate pilot behind gas valve mounted on the base panel of the burner drawer.

7.Turn knob on gas control counter-clockwise

to "Pilot".

GASCONTROL

KNOBSHOWN

IN"OFF"

POSITION

GASINLET

5.Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow "B" in the safety information above on this label. If you don't smell gas, go to the next step.

6.Locate pilot behind gas valve, mounted on the base panel of the burner drawer.

7.Turn knob on gas control counter-clockwise

to "PILOT".

Fig.# 8083.2

Fig.# 8041.2

HONEYWELL PILOT

ROBERTSHAW PILOT

Fig.# 8083.2

Fig.# 8041.2

HONEYWELLPILOT

ROBERTSHAW PILOT

14