CONTROL FUNCTIONS

RESET RATIO

The Reset Ratio setting determines how much the Target Temperature will increase as the outdoor temperature drops. The Reset Ratio is expressed in the following manner:

X:Y

X - change in outdoor temperature

 

Y - change in Target Temperature

The first number in the ratio refers to the change in outdoor temperature in degrees Fahren- heit below outdoor cutoff while the second refers to the change in the computed Target Temperature in degrees Fahrenheit. A Reset Ratio of 2:1 means that for every 2°F drop in outdoor temperature from 70°F, the Target Temperature will increase 1°F.

For example:

Assume a Reset Ratio setting of 2:1 and a Set Point of 120°F.

When the outdoor temperature drops from 70°F to 20°F, the Target Temperature will in- crease from 120°F to 145°F. (With an outdoor to target ratio of 2:1, a 50°F outdoor tem- perature decrease results in a 25°F Target Temperature increase). See Reset Ratio Chart (pg. 20) for more information.

The Reset Ratio is adjustable from 0.12:1 to 8.0:1.

Recommended Initial Setting for Reset Ratio is 1:1.

Suggested Settings

 

Typical

Reset Ratio Setpoint at Design Temp:

RADIATION

Temp @

Temp. @

40°F

20°F

0°F

- 20°F

Design Cond.

70°F

 

 

 

 

 

Standing

190

105

0.3:1

0.6:1

0.8:1

1.1:1

 

 

 

 

 

 

 

Convection or

200

105

0.3:1

0.5:1

0.7:1

0.9:1

Baseboard

 

 

 

 

 

 

Fan Coil - Heating

190

105

0.3:1

0.6:1

0.8:1

1.1:1

 

 

 

 

 

 

 

Fan Coil - Heat & Cool

140

105

0.9:1

1.4:1

2.0:1

2.6:1

 

 

 

 

 

 

 

Radiant Floor

120

105

2.0:1

3.3:1

4.7:1

6.0:1

 

 

 

 

 

 

 

Radiant Ceiling

120

105

2.0:1

3.3:1

4.7:1

6.0:1

 

 

 

 

 

 

 

The selection of the correct ratio is dependent on the initial temperature Set Point and the desired system water temperature. If the building is too cold, move the ratio knob counter-clockwise one setting. After a change is made to the ratio, wait several days and evaluate the comfort level before making another change.