Raypak 240692 manual Wiring Power Source to Controller, Checkyourpowersource

Models: 240692

1 31
Download 31 pages 11.83 Kb
Page 8
Image 8

CHECKYOURPOWERSOURCE

Using a volt-ohm meter, check the following voltages at the circuit breaker panel:

BLACK CIRCUIT

BREAKER

WHITE

GREEN

GROUND

A B C

AC = 108 Volts AC Minimum, 132 Volts MAX AB = 108 Volts AC Minimum, 132 Volts MAX BC = Must be less than 1.0 Volts AC

VOLT-OHM

METER

WIRING: POWER SOURCE TO CONTROLLER

Observe polarity.

Observe proper wire colors while making electrical connections.

Provide an external surge suppressor capable of maintaining system integrity.

Provide overload protection and a disconnect means for equipment serviceability as required by local and state code.

Conduit cannot be used as the ground. (There must be a “WIRED” ground.)

Very Important: A grounding electrode conductor shall be used to connect the equipment grounding conductors, the equipment enclosures, and where the system is grounded, the grounded service conductor to the grounding electrode.

GRN

120VAC

HOT

WHT

RTN

SUPPLY

 

GND

 

 

BLK

 

 

 

 

GRN

 

 

WHT

 

 

BLK

SPG

SINGLE POINT

GROUND

8

Page 8
Image 8
Raypak 240692 manual Wiring Power Source to Controller, Checkyourpowersource