BOILER
The Boiler
The Boiler
Recommended Initial Setting for Boiler
STAGE TURN-ON DELAY
The Stage
The Stage
Recommended Initial Setting Stage for
CONTROL BAND
The Control Band sets the maximum temperature above or below the Target Temperature (which is determined by the embedded
The Control Band range is from 1°F to 10°F.
Recommended Initial Setting for Control Band is 3°F.
OUTDOOR CUTOFF DEADBAND
The Outdoor Cutoff Deadband sets the number of degrees below the Outdoor Cutoff where the Outdoor Cutoff reset occurs.
The Outdoor Cutoff Deadband range is from 1°F to 10°F.
Recommended Initial Setting for Outdoor Cutoff Deadband is 3°F.
OUTDOOR CUTOFF TEMPERATURE
The Outdoor Cutoff sets the maximum outdoor temperature at which heat is desired. This control sets the outdoor temperature above which the boiler bank is disabled. If the out- door temperature increases beyond the Outdoor Cutoff setting, the Control ON LED turns off and if there is no call for heat, the pump
The Outdoor Cutoff Temperature is from 32°F to 200°F. Recommended Initial Setting for Outdoor Cutoff Temperature is 65°F.