MAXIMUM WATER TEMPERATURE

MAXIMUM WATER TEMPERATURE

The Maximum Output Temperature is the system output high limit. This potentiometer sets the maximum value the Target Temperature is allowed to reach regardless of other operational settings or conditions.

The Maximum Water Temperature range is from 70°F to 235°F. Recommended Initial Setting for Maximum Water Temperature is 180°F.

SET POINT

The Set Point is the system output temperature desired when the outdoor temperature is 70°F. This potentiometer may be set to any temperature from 40°F to 220°F, and is the base-line setting for all operations. Note: Set Point cannot be below 105°F in normal operation unless the No Min Set Point switch is in the ON position. (See Mode Selector Switch). In domestic water supply applications, Set Point determines the water tem- perature maintained by the control.

The Set Point range is from 40°F to 220°F. Recommended Initial Setting Set for Point is 120°F.

CAUTION: Setting the Set Point below 105°F may cause the boiler to condense which will damage the boiler.