Raypak B0109, B0147 Burner Pressure Adjustment, Gas Inlet Pressure, 147 On/Off Models

Models: B0109 B0147

1 43
Download 43 pages 45.6 Kb
Page 33
Image 33
BURNER PRESSURE ADJUSTMENT

BURNER PRESSURE ADJUSTMENT

GAS INLET PRESSURE

IMPORTANT – CHECK the gas supply pressure at the inlet to the water heater with the water heater and all other gas burning appliances in the premises operating (burners alight). The minimum gas supply pressures are:

Natural Gas - 1.13 kPa

Propane - 2.75 kPa

If this minimum cannot be achieved, it may indicate the meter or the gas line to the water heater is undersized. It is important to ensure that an adequate gas supply pressure is available to the water heater when other gas burning appliances, on the same gas supply, are operating.

GAS PRESSURE ADJUSTMENT 109 On/Off Models

To adjust the burner pressure on a water heater with a White Rodgers 36G22 Type 210 gas valve proceed as follows:

Remove the screw from the outlet pressure tap.

Attach a manometer to the outlet pressure tap.

Remove the cap from the pressure regulator adjuster.

With the main burner operating, adjust the pressure regulator (clockwise to increase or anti-clockwise to decrease) to achieve the burner pressure as specified on the rating label (refer to “Location of Controls” on page 29).

Turn off the water heater.

Replace the cap on the pressure regulator adjuster.

Regulator Cap

Pressure Tap

 

 

Disconnect the manometer and replace the pressure tap screw and washer.

Check for gas leaks, using soapy water.

147 On/Off Models

 

 

To adjust the burner pressure on a water heater with a Honeywell Smart

Regulator Cap

Pressure Tap

Valve, proceed as follows:

Remove the screw and washer from the outlet pressure tap.

Attach a manometer to the outlet pressure tap.

Remove the cap from the pressure regulator adjuster.

With the main burner operating, adjust the pressure regulator (clockwise to increase or anti-clockwise to decrease) to achieve the burner pressure as specified on the rating label (refer to “Location of Controls” on page 29).

Turn off the water heater.

Replace the cap on the pressure regulator adjuster.

Disconnect the manometer and replace the pressure tap screw and washer.

Check for gas leaks, using soapy water.

33

Page 33
Image 33
Raypak B0109 Burner Pressure Adjustment, Gas Inlet Pressure, GAS PRESSURE ADJUSTMENT 109 On/Off Models, 147 On/Off Models