MECHANICAL HEATING

CONNECTIONS - PLUMBING

MECHANICAL HEATING

All high points of a mechanical heating system should be provided with manual bleed points or fitted with automatic air vents. The design of the system must be such that the water heater is provided with adequate water flow and pressure at all times (refer to ‘Pump Selection’ on page 20. On radiator or heating systems where thermostatic valves will vary the water flow a suitable by-pass valve must be installed to maintain the correct flow rate.

Typical Mechanical Heating Installation

WATER HEATING

Where the water heater is supplied as part of a package, including the storage cylinder and pump, the installation must comply with the drawing provided. Failure to observe this requirement may result in ineffective hot water capacity or damage.

Typical Water Heating Installation

21

Page 21
Image 21
Raypak B0109, B0147 Typical Mechanical Heating Installation, Typical Water Heating Installation