11.5.0Diagnostics

11.5.0Diagnostics

Several hardware diagnostics capabilities have been implemented using the LED indicator lights on the front of the T-3 card. The possible conditions as indicated by the lights are:

11.5.1LED Indicators

Several hardware diagnostics capabilities have been implemented using the LED indicator lights on the front of the module. The possible conditions as indicated by the lights are:

 

 

 

 

 

 

 

 

Name

LED

Color

Status

Indication

 

 

Modbus (P1)

D1

Green

Blinking

The T-3 is receiving a command

 

 

ACTIVE

 

 

 

from the Modbus Host

 

 

 

 

 

Steady

The T-3 is not detecting a valid

 

 

 

 

 

ON

command. If the master is

 

 

 

 

 

or

transmitting, be sure all dip

 

 

 

 

 

OFF

switches are set correctly and that

 

 

 

 

 

 

the cable connection is correct.

 

 

Raypak (P2)

D2

Green

Blinking

The T-3is processing a B6000

 

 

ACTIVE

 

 

 

command

 

 

 

 

 

Steady

Check cable connection to verify

 

 

 

 

 

ON

polarity of terminations between

 

 

 

 

 

or

T-3 card and B6000 (See Appen-

 

 

 

 

 

OFF

dix B)

 

 

Modbus (P1)

D3

Red

ON

The Modbus port has detected a

 

 

COMM

 

 

or

communications error condition.

 

 

ERR

 

 

Blinking

See Section 4.2

 

 

 

 

 

 

 

 

 

 

 

 

OFF

No error conditions at this time.

 

 

Raypak (P2)

D4

Red

ON

The T-3 card has detected a

 

 

FAULT

 

 

 

communications error condition.

 

 

 

 

 

OFF

No error conditions at this time.

 

Should the configuration dip switches select an invalid address or an invalid baud rate, the LED indicators will alternate in the on/off fashion on 1/2 second intervals until correct values are selected.