| 30049 | 40049 | bit | Boiler #6 Status Word | Boiler #6 |
|
R | 10289 |
| 0 | Boiler Not On Line |
| (0 = Normal, 1 = Alarm) |
R | 10290 |
| 1 | Boiler Operation |
| (0 = Firing, 1 = Ready) |
R | 10291 |
| 2 | Low Water Cutoff |
| (0 = Normal, 1 = Alarm) |
R | 10292 |
| 3 | Low Pressure Water |
| (0 = Normal, 1 = Alarm) |
R | 10293 |
| 4 | Low Pressure Gas |
| (0 = Normal, 1 = Alarm) |
R | 10294 |
| 5 | High Pressure Gas |
| (0 = Normal, 1 = Alarm) |
R | 10295 |
| 6 | High Limit |
| (0 = Normal, 1 = Alarm) |
R | 10296 |
| 7 | Thermostat - Operating aquastat (not fault) | (0 = Normal, 1 = Aquastat) | |
R | 10297 |
| 8 | Manual Override |
| (0 = Normal, 1 = Alarm) |
R | 10298 |
| 9 | Flow Switch |
| (0 = Normal, 1 = Alarm) |
R | 10299 |
| 10 | No Pilot |
| (0 = Normal, 1 = Alarm) |
| 30050 | 40050 | bit | Boiler #7 Status Ward | Boiler #7 |
|
R | 10305 |
| 0 | Boiler Not On Line |
| (0 = Normal, 1 = Alarm) |
R | 10306 |
| 1 | Boiler Operation |
| (0 = Firing, 1 = Ready) |
R | 10307 |
| 2 | Low Water Cutoff |
| (0 = Normal, 1 = Alarm) |
R | 10308 |
| 3 | Low Pressure Water |
| (0 = Normal, 1 = Alarm) |
R | 10309 |
| 4 | Low Pressure Gas |
| (0 = Normal, 1 = Alarm) |
R | 10310 |
| 5 | High Pressure Gas |
| (0 = Normal, 1 = Alarm) |
R | 10311 |
| 6 | High Limit |
| (0 = Normal, 1 = Alarm) |
R | 10312 |
| 7 | Thermostat - Operating aquastat (not fault) | (0 = Normal, 1 = Aquastat) | |
R | 10313 |
| 8 | Manual Override |
| (0 = Normal, 1 = Alarm) |
R | 10314 |
| 9 | Flow Switch |
| (0 = Normal, 1 = Alarm) |
R | 10315 |
| 10 | No Pilot |
| (0 = Normal, 1 = Alarm) |
| 30035 | 40051 | bit | Boiler #3 Status Ward | Boiler #8 |
|
R | 10321 |
| 0 | Boiler Not On Line |
| (0 = Normal, 1 = Alarm) |
R | 10322 |
| 1 | Boiler Operation |
| (0 = Firing, 1 = Ready) |
R | 10323 |
| 2 | Low Water Cutoff |
| (0 = Normal, 1 = Alarm) |
R | 10324 |
| 3 | Low Pressure Water |
| (0 = Normal, 1 = Alarm) |
R | 10325 |
| 4 | Low Pressure Gas |
| (0 = Normal, 1 = Alarm) |
R | 10326 |
| 5 | High Pressure Gas |
| (0 = Normal, 1 = Alarm) |
R | 10327 |
| 6 | High Limit |
| (0 = Normal, 1 = Alarm) |
R | 10328 |
| 7 | Thermostat - Operating aquastat (not fault) | (0 = Normal, 1 = Aquastat) | |
R | 10329 |
| 8 | Manual Override |
| (0 = Normal, 1 = Alarm) |
R | 10330 |
| 9 | Flow Switch |
| (0 = Normal, 1 = Alarm) |
R | 10331 |
| 10 | No Pilot |
| (0 = Normal, 1 = Alarm) |
R | 30052 | 40052 | Setpoint | Day Setpoint (Desired water temp @70F) | |
R | 30053 | 40053 | Nitesetback Night Setback (Desired water temp @ 70F) | ||
R | 30054 | 40054 | Ratio Out | ||
R | 30055 | 40055 | Throttling Delta T of all boilers in system (Normally 20 / # boilers) | ||
R | 30056 | 40056 | Modulating Step (%) min 5% steps | ||
R | 30057 | 40057 | Wait State Time (Sec) | ||
R | 30058 | 40058 | Outdoor Cut off Temperature (O/C) | ||
R | 30059 | 40059 | Control Band (degrees F Tolerance from TAR) (C/B) | ||
R | 30060 | 40060 | Lead Boiler Number (1 to Number of Boilers) | ||
R | 30061 | 40061 | Number of Boilers | ||
R | 30062 | 40062 | TP - Boiler Pump Delays (Min) Boiler #1 | ||
R | 30063 | 40063 | TP - Boiler Pump Delays (Min) Boiler #2 | ||
R | 30064 | 40064 | TP - | Boiler Pump Delays (Min) Boiler #3 | |
R | 30065 | 40065 | TP - | Boiler Pump Delays (Min) Boiler #4 | |
R | 30066 | 40066 | TP - | Boiler Pump Delays (Min) Boiler #5 | |
R | 30067 | 40067 | TP - | Boiler Pump Delays (Min) Boiler #6 | |
R | 30068 | 40068 |
| TP - | Boiler Pump Delays (Min) Boiler #7 |
R | 30069 | 40069 |
| TP - | Boiler Pump Delays (Min) Boiler #8 |
22