Raypak B6000 manual Boiler #6

Models: B6000

1 24
Download 24 pages 53.62 Kb
Page 22
Image 22

 

30049

40049

bit

Boiler #6 Status Word

Boiler #6

 

R

10289

 

0

Boiler Not On Line

 

(0 = Normal, 1 = Alarm)

R

10290

 

1

Boiler Operation

 

(0 = Firing, 1 = Ready)

R

10291

 

2

Low Water Cutoff

 

(0 = Normal, 1 = Alarm)

R

10292

 

3

Low Pressure Water

 

(0 = Normal, 1 = Alarm)

R

10293

 

4

Low Pressure Gas

 

(0 = Normal, 1 = Alarm)

R

10294

 

5

High Pressure Gas

 

(0 = Normal, 1 = Alarm)

R

10295

 

6

High Limit

 

(0 = Normal, 1 = Alarm)

R

10296

 

7

Thermostat - Operating aquastat (not fault)

(0 = Normal, 1 = Aquastat)

R

10297

 

8

Manual Override

 

(0 = Normal, 1 = Alarm)

R

10298

 

9

Flow Switch

 

(0 = Normal, 1 = Alarm)

R

10299

 

10

No Pilot

 

(0 = Normal, 1 = Alarm)

 

30050

40050

bit

Boiler #7 Status Ward

Boiler #7

 

R

10305

 

0

Boiler Not On Line

 

(0 = Normal, 1 = Alarm)

R

10306

 

1

Boiler Operation

 

(0 = Firing, 1 = Ready)

R

10307

 

2

Low Water Cutoff

 

(0 = Normal, 1 = Alarm)

R

10308

 

3

Low Pressure Water

 

(0 = Normal, 1 = Alarm)

R

10309

 

4

Low Pressure Gas

 

(0 = Normal, 1 = Alarm)

R

10310

 

5

High Pressure Gas

 

(0 = Normal, 1 = Alarm)

R

10311

 

6

High Limit

 

(0 = Normal, 1 = Alarm)

R

10312

 

7

Thermostat - Operating aquastat (not fault)

(0 = Normal, 1 = Aquastat)

R

10313

 

8

Manual Override

 

(0 = Normal, 1 = Alarm)

R

10314

 

9

Flow Switch

 

(0 = Normal, 1 = Alarm)

R

10315

 

10

No Pilot

 

(0 = Normal, 1 = Alarm)

 

30035

40051

bit

Boiler #3 Status Ward

Boiler #8

 

R

10321

 

0

Boiler Not On Line

 

(0 = Normal, 1 = Alarm)

R

10322

 

1

Boiler Operation

 

(0 = Firing, 1 = Ready)

R

10323

 

2

Low Water Cutoff

 

(0 = Normal, 1 = Alarm)

R

10324

 

3

Low Pressure Water

 

(0 = Normal, 1 = Alarm)

R

10325

 

4

Low Pressure Gas

 

(0 = Normal, 1 = Alarm)

R

10326

 

5

High Pressure Gas

 

(0 = Normal, 1 = Alarm)

R

10327

 

6

High Limit

 

(0 = Normal, 1 = Alarm)

R

10328

 

7

Thermostat - Operating aquastat (not fault)

(0 = Normal, 1 = Aquastat)

R

10329

 

8

Manual Override

 

(0 = Normal, 1 = Alarm)

R

10330

 

9

Flow Switch

 

(0 = Normal, 1 = Alarm)

R

10331

 

10

No Pilot

 

(0 = Normal, 1 = Alarm)

R

30052

40052

Setpoint

Day Setpoint (Desired water temp @70F)

R

30053

40053

Nitesetback Night Setback (Desired water temp @ 70F)

R

30054

40054

Ratio Out

1-200 = 0.1 - 20.0 in 0.1 increments

R

30055

40055

Throttling Delta T of all boilers in system (Normally 20 / # boilers)

R

30056

40056

Modulating Step (%) min 5% steps

R

30057

40057

Wait State Time (Sec)

R

30058

40058

Outdoor Cut off Temperature (O/C)

R

30059

40059

Control Band (degrees F Tolerance from TAR) (C/B)

R

30060

40060

Lead Boiler Number (1 to Number of Boilers)

R

30061

40061

Number of Boilers

R

30062

40062

TP - Boiler Pump Delays (Min) Boiler #1

R

30063

40063

TP - Boiler Pump Delays (Min) Boiler #2

R

30064

40064

TP -

Boiler Pump Delays (Min) Boiler #3

R

30065

40065

TP -

Boiler Pump Delays (Min) Boiler #4

R

30066

40066

TP -

Boiler Pump Delays (Min) Boiler #5

R

30067

40067

TP -

Boiler Pump Delays (Min) Boiler #6

R

30068

40068

 

TP -

Boiler Pump Delays (Min) Boiler #7

R

30069

40069

 

TP -

Boiler Pump Delays (Min) Boiler #8

A-4

22

Page 22
Image 22
Raypak B6000 manual Boiler #6