Raypak Modbus Register Assignments |
|
|
|
|
|
| ||||||
| Function Function Function |
|
|
|
|
|
| |||||
Type | 2 | 4 | 3,6 |
| Description |
|
|
| ||||
R/W |
|
|
|
|
| 40001 |
| Setpoint | Day Setpoint (Desired water temp @70F) | |||
|
|
| 30001 |
| ||||||||
R/W |
|
| 30002 | 40002 |
| Nitesetback | Night Setback (Desired water temp @ 70F) | |||||
R/W |
|
| 30003 | 40003 |
| Ratio Out | ||||||
R/W |
|
| 30004 | 40004 |
| Throttling Delta T of all boilers in system (Normally 20 / # boilers) | ||||||
R/W |
|
| 30005 | 40005 |
| Modulating Step (%) min 5% steps |
| |||||
R/W |
|
| 30006 | 40006 |
| Wait State Time (Sec) |
|
| ||||
R/W |
|
| 30007 | 40007 |
| Outdoor Cut off Temperature (O/C) |
| |||||
R/W |
|
| 30008 | 40008 |
| Control Band (degrees F Tolerance from TAR) (C/B) | ||||||
R/W |
|
| 30009 | 40009 |
| Lead Boiler Number (1 to Number of Boilers) | ||||||
R/W |
|
| 30010 | 40010 |
| Number of Boilers |
|
| ||||
R/W |
|
| 30011 | 40011 |
| TP - Boiler Pump Delay (Min) Boiler #1 |
| |||||
R/W |
|
| 30012 | 40012 |
| TP - Boiler Pump Delay (Min) Boiler #2 |
| |||||
R/W |
|
| 30013 | 40013 |
| TP- | Boiler Pump Delay (Min) Boiler #3 |
| ||||
R/W |
|
| 30014 | 40014 |
| TP- | Boiler Pump Delay (Min) Boiler #4 |
| ||||
R/W |
|
| 30015 | 40015 |
| TP- | Boiler Pump Delay (Min) Boiler #5 |
| ||||
R/W |
|
| 30016 | 40016 |
| TP- | Boiler Pump Delay (Min) Boiler #6 |
| ||||
R/W |
|
| 30017 | 40017 |
| TP- | Boiler Pump Delay (Min) Boiler #7 |
| ||||
R/W |
|
| 30018 | 40018 |
| TP- | Boiler Pump Delay (Min) Boiler #8 |
| ||||
R/W |
|
| 30019 | 40019 |
| TS - Ignition Time (Sec) Boiler #1 |
| |||||
R/W |
|
| 30020 | 40020 |
| TS - Ignition Time (Sec) Boiler #2 |
| |||||
R/W |
|
| 30021 | 40021 |
| TS - Ignition Time (Sec) Boiler #3 |
| |||||
R/W |
|
| 30022 | 40022 |
| TS - Ignition Time (Sec) Boiler #4 |
| |||||
R/W |
|
| 30023 | 40023 |
| TS - Ignition Time (Sec) Boiler #5 |
| |||||
R/W |
|
| 30024 | 40024 |
| TS - Ignition Time (Sec) Boiler #6 |
| |||||
R/W |
|
| 30025 | 40025 |
| TS - Ignition Time (Sec) Boiler #7 |
| |||||
R/W |
|
| 30026 | 40026 |
| TS - Ignition Time (Sec) Boiler #8 |
| |||||
R/W |
|
| 30027 | 40027 |
| Time - Hrs |
|
|
| |||
R/W |
|
| 30028 | 40028 |
| Time - Min |
|
|
| |||
R/W |
|
| 30029 | 40029 |
| Time - DWK |
|
|
| |||
R/W |
|
| 30030 | 40030 |
| Lead Change Hours |
|
| ||||
R | 10001 | 30031 | 40031 |
| Bit 0 = Night Setback on |
| Night Setback | |||||
R | 10017 | 30032 | 40032 |
| Bit 0 = Fault Status )1=system fault) | Controller LED Status | ||||||
R | 10018 |
|
|
|
|
| Bit 1 = Call Out Request (1 = Yes) | Controller LED Status | ||||
R |
|
| 30033 | 40033 |
| Outdoor Temperature + 35 |
|
| ||||
R |
|
| 30034 | 40034 |
| Water Temperature + 35 |
|
| ||||
R |
|
| 30035 | 40035 |
| Target Temperature (TAR) |
|
| ||||
R |
|
| 30036 | 40036 |
| Valve Position |
| |||||
R |
|
| 30037 | 40037 |
| Valve Position |
| |||||
R |
|
| 30038 | 40038 |
| Valve Position |
| |||||
R |
|
| 30039 | 40039 |
| Valve Position |
| |||||
R |
|
| 30040 | 40040 |
| Valve Position |
| |||||
R |
|
| 30041 | 40041 |
| Valve Position |
| |||||
R |
|
| 30042 | 40042 |
| Valve Position |
| |||||
R |
|
| 30043 | 40043 |
| Valve Position |
| |||||
|
|
| 30044 | 40044 | bit | Boiler #1 Status Word | Boiler #1 |
| ||||
|
|
|
|
|
|
|
|
|
|
|
| |
R | 10209 |
|
|
|
| 0 Boiler Not On Line |
| (0 = Normal, 1 = Alarm) | ||||
R | 10210 |
|
|
|
| 1 | Boiler Operation |
| (0 = Firing, 1 = Ready) | |||
R | 10211 |
|
|
|
| 2 | Low Water Cutoff |
| (0 = Normal, 1 = Alarm) | |||
R | 10212 |
|
|
|
| 3 | Low Pressure Water |
| (0 = Normal, 1 = Alarm) | |||
R | 10213 |
|
|
|
| 4 | Low Pressure Gas |
| (0 = Normal, 1 = Alarm) | |||
R | 10214 |
|
|
|
| 5 | High Pressure Gas |
| (0 = Normal, 1 = Alarm) | |||
|
|
|
|
|
|
|
|
|
|
|
|
20