Raypak Modbus Register Assignments

 

 

 

 

 

 

 

Function Function Function

 

 

 

 

 

 

Type

2

4

3,6

 

Description

 

 

 

R/W

 

 

 

 

 

40001

 

Setpoint

Day Setpoint (Desired water temp @70F)

 

 

 

30001

 

R/W

 

 

30002

40002

 

Nitesetback

Night Setback (Desired water temp @ 70F)

R/W

 

 

30003

40003

 

Ratio Out

1-200 = 0.1 - 20.0 in 0.1 increments

R/W

 

 

30004

40004

 

Throttling Delta T of all boilers in system (Normally 20 / # boilers)

R/W

 

 

30005

40005

 

Modulating Step (%) min 5% steps

 

R/W

 

 

30006

40006

 

Wait State Time (Sec)

 

 

R/W

 

 

30007

40007

 

Outdoor Cut off Temperature (O/C)

 

R/W

 

 

30008

40008

 

Control Band (degrees F Tolerance from TAR) (C/B)

R/W

 

 

30009

40009

 

Lead Boiler Number (1 to Number of Boilers)

R/W

 

 

30010

40010

 

Number of Boilers

 

 

R/W

 

 

30011

40011

 

TP - Boiler Pump Delay (Min) Boiler #1

 

R/W

 

 

30012

40012

 

TP - Boiler Pump Delay (Min) Boiler #2

 

R/W

 

 

30013

40013

 

TP-

Boiler Pump Delay (Min) Boiler #3

 

R/W

 

 

30014

40014

 

TP-

Boiler Pump Delay (Min) Boiler #4

 

R/W

 

 

30015

40015

 

TP-

Boiler Pump Delay (Min) Boiler #5

 

R/W

 

 

30016

40016

 

TP-

Boiler Pump Delay (Min) Boiler #6

 

R/W

 

 

30017

40017

 

TP-

Boiler Pump Delay (Min) Boiler #7

 

R/W

 

 

30018

40018

 

TP-

Boiler Pump Delay (Min) Boiler #8

 

R/W

 

 

30019

40019

 

TS - Ignition Time (Sec) Boiler #1

 

R/W

 

 

30020

40020

 

TS - Ignition Time (Sec) Boiler #2

 

R/W

 

 

30021

40021

 

TS - Ignition Time (Sec) Boiler #3

 

R/W

 

 

30022

40022

 

TS - Ignition Time (Sec) Boiler #4

 

R/W

 

 

30023

40023

 

TS - Ignition Time (Sec) Boiler #5

 

R/W

 

 

30024

40024

 

TS - Ignition Time (Sec) Boiler #6

 

R/W

 

 

30025

40025

 

TS - Ignition Time (Sec) Boiler #7

 

R/W

 

 

30026

40026

 

TS - Ignition Time (Sec) Boiler #8

 

R/W

 

 

30027

40027

 

Time - Hrs

 

 

 

R/W

 

 

30028

40028

 

Time - Min

 

 

 

R/W

 

 

30029

40029

 

Time - DWK

 

 

 

R/W

 

 

30030

40030

 

Lead Change Hours

 

 

R

10001

30031

40031

 

Bit 0 = Night Setback on

 

Night Setback

R

10017

30032

40032

 

Bit 0 = Fault Status )1=system fault)

Controller LED Status

R

10018

 

 

 

 

 

Bit 1 = Call Out Request (1 = Yes)

Controller LED Status

R

 

 

30033

40033

 

Outdoor Temperature + 35

 

 

R

 

 

30034

40034

 

Water Temperature + 35

 

 

R

 

 

30035

40035

 

Target Temperature (TAR)

 

 

R

 

 

30036

40036

 

Valve Position (0-100%) - Boiler #1

 

R

 

 

30037

40037

 

Valve Position (0-100%) - Boiler #2

 

R

 

 

30038

40038

 

Valve Position (0-100%) - Boiler #3

 

R

 

 

30039

40039

 

Valve Position (0-100%) - Boiler #4

 

R

 

 

30040

40040

 

Valve Position (0-100%) - Boiler #5

 

R

 

 

30041

40041

 

Valve Position (0-100%) - Boiler #6

 

R

 

 

30042

40042

 

Valve Position (0-100%) - Boiler #7

 

R

 

 

30043

40043

 

Valve Position (0-100%) - Boiler #8

 

 

 

 

30044

40044

bit

Boiler #1 Status Word

Boiler #1

 

 

 

 

 

 

 

 

 

 

 

 

 

R

10209

 

 

 

 

0 Boiler Not On Line

 

(0 = Normal, 1 = Alarm)

R

10210

 

 

 

 

1

Boiler Operation

 

(0 = Firing, 1 = Ready)

R

10211

 

 

 

 

2

Low Water Cutoff

 

(0 = Normal, 1 = Alarm)

R

10212

 

 

 

 

3

Low Pressure Water

 

(0 = Normal, 1 = Alarm)

R

10213

 

 

 

 

4

Low Pressure Gas

 

(0 = Normal, 1 = Alarm)

R

10214

 

 

 

 

5

High Pressure Gas

 

(0 = Normal, 1 = Alarm)

A-2

 

 

 

 

 

 

 

 

 

 

 

 