R | 10215 |
| 6 | High Limit |
| (0 = Normal, 1 = Alarm) |
R | 10216 |
| 7 | Thermostat - Operating aquastat (not fault) | (0 = Normal, 1 = Aquastat) | |
R | 10217 |
| 8 | Manual Override |
| (0 = Normal, 1 = Alarm) |
R | 10218 |
| 9 | Flow Switch |
| (0 = Normal, 1 = Alarm) |
R | 10219 |
| 10 | No Pilot |
| (0 = Normal, 1 = Alarm) |
| 30045 | 40045 | bit | Boiler #2 Status Word | Boiler #2 |
|
R | 10225 |
| 0 | Boiler Not On Line |
| (0 = Normal, 1 = Alarm) |
R | 10226 |
| 1 | Boiler Operation |
| (0 = Firing, 1 = Ready) |
R | 10227 |
| 2 | Low Water Cutoff |
| (0 = Normal, 1 = Alarm) |
R | 10228 |
| 3 | Low Pressure Water |
| (0 = Normal, 1 = Alarm) |
R | 10229 |
| 4 | Low Pressure Gas |
| (0 = Normal, 1 = Alarm) |
R | 10230 |
| 5 | High Pressure Gas |
| (0 = Normal, 1 = Alarm) |
R | 10231 |
| 6 | High Limit |
| (0 = Normal, 1 = Alarm) |
R | 10232 |
| 7 | Thermostat - Operating aquastat (not fault) | (0 = Normal, 1 = Aquastat) | |
R | 10233 |
| 8 | Manual Override |
| (0 = Normal, 1 = Alarm) |
R | 10234 |
| 9 | Flow Switch |
| (0 = Normal, 1 = Alarm) |
R | 10235 |
| 10 | No Pilot |
| (0 = Normal, 1 = Alarm) |
| 30046 | 40046 | bit | Boiler #3 Status Word | Boiler #3 |
|
R | 10241 |
| 0 | Boiler Not On Line |
| (0 = Normal, 1 = Alarm) |
R | 10242 |
| 1 | Boiler Operation |
| (0 = Firing, 1 = Ready) |
R | 10243 |
| 2 | Low Water Cutoff |
| (0 = Normal, 1 = Alarm) |
R | 10244 |
| 3 | Low Pressure Water |
| (0 = Normal, 1 = Alarm) |
R | 10245 |
| 4 | Low Pressure Gas |
| (0 = Normal, 1 = Alarm) |
R | 10246 |
| 5 | High Pressure Gas |
| (0 = Normal, 1 = Alarm) |
R | 10247 |
| 6 | High Limit |
| (0 = Normal, 1 = Alarm) |
R | 10248 |
| 7 | Thermostat - Operating aquastat (not fault) | (0 = Normal, 1 = Aquastat) | |
R | 10249 |
| 8 | Manual Override |
| (0 = Normal, 1 = Alarm) |
R | 10250 |
| 9 | Flow Switch |
| (0 = Normal, 1 = Alarm) |
R | 10251 |
| 10 | No Pilot |
| (0 = Normal, 1 = Alarm) |
| 30047 | 40047 | bit | Boiler #4 Status Word | Boiler #4 |
|
R | 10257 |
| 0 | Boiler Not On Line |
| (0 = Normal, 1 = Alarm) |
R | 10258 |
| 1 | Boiler Operation |
| (0 = Firing, 1 = Ready) |
R | 10259 |
| 2 | Low Water Cutoff |
| (0 = Normal, 1 = Alarm) |
R | 10260 |
| 3 | Low Pressure Water |
| (0 = Normal, 1 = Alarm) |
R | 10261 |
| 4 | Low Pressure Gas |
| (0 = Normal, 1 = Alarm) |
R | 10262 |
| 5 | High Pressure Gas |
| (0 = Normal, 1 = Alarm) |
R | 10263 |
| 6 | High Limit |
| (0 = Normal, 1 = Alarm) |
R | 10264 |
| 7 | Thermostat - Operating aquastat (not fault) | (0 = Normal, 1 = Aquastat) | |
R | 10265 |
| 8 | Manual Override |
| (0 = Normal, 1 = Alarm) |
R | 10266 |
| 9 | Flow Switch |
| (0 = Normal, 1 = Alarm) |
R | 10267 |
| 10 | No Pilot |
| (0 = Normal, 1 = Alarm) |
| 30048 | 40048 | bit | Boiler #3 Status Word | Boiler #5 |
|
R | 10273 |
| 0 | Boiler Not On Line |
| (0 = Normal, 1 = Alarm) |
R | 10274 |
| 1 | Boiler Operation |
| (0 = Firing, 1 = Ready) |
R | 10275 |
| 2 | Low Water Cutoff |
| (0 = Normal, 1 = Alarm) |
R | 10276 |
| 3 | Low Pressure Water |
| (0 = Normal, 1 = Alarm) |
R | 10277 |
| 4 | Low Pressure Gas |
| (0 = Normal, 1 = Alarm) |
R | 10278 |
| 5 | High Pressure Gas |
| (0 = Normal, 1 = Alarm) |
R | 10279 |
| 6 | High Limit |
| (0 = Normal, 1 = Alarm) |
R | 10280 |
| 7 | Thermostat - Operating aquastat (not fault) | (0 = Normal, 1 = Aquastat) | |
R | 10281 |
| 8 | Manual Override |
| (0 = Normal, 1 = Alarm) |
R | 10282 |
| 9 | Flow Switch |
| (0 = Normal, 1 = Alarm) |
R | 10283 |
| 10 | No Pilot |
| (0 = Normal, 1 = Alarm) |
21