Raypak B6000 manual Boiler #2

Models: B6000

1 24
Download 24 pages 53.62 Kb
Page 21
Image 21

R

10215

 

6

High Limit

 

(0 = Normal, 1 = Alarm)

R

10216

 

7

Thermostat - Operating aquastat (not fault)

(0 = Normal, 1 = Aquastat)

R

10217

 

8

Manual Override

 

(0 = Normal, 1 = Alarm)

R

10218

 

9

Flow Switch

 

(0 = Normal, 1 = Alarm)

R

10219

 

10

No Pilot

 

(0 = Normal, 1 = Alarm)

 

30045

40045

bit

Boiler #2 Status Word

Boiler #2

 

R

10225

 

0

Boiler Not On Line

 

(0 = Normal, 1 = Alarm)

R

10226

 

1

Boiler Operation

 

(0 = Firing, 1 = Ready)

R

10227

 

2

Low Water Cutoff

 

(0 = Normal, 1 = Alarm)

R

10228

 

3

Low Pressure Water

 

(0 = Normal, 1 = Alarm)

R

10229

 

4

Low Pressure Gas

 

(0 = Normal, 1 = Alarm)

R

10230

 

5

High Pressure Gas

 

(0 = Normal, 1 = Alarm)

R

10231

 

6

High Limit

 

(0 = Normal, 1 = Alarm)

R

10232

 

7

Thermostat - Operating aquastat (not fault)

(0 = Normal, 1 = Aquastat)

R

10233

 

8

Manual Override

 

(0 = Normal, 1 = Alarm)

R

10234

 

9

Flow Switch

 

(0 = Normal, 1 = Alarm)

R

10235

 

10

No Pilot

 

(0 = Normal, 1 = Alarm)

 

30046

40046

bit

Boiler #3 Status Word

Boiler #3

 

R

10241

 

0

Boiler Not On Line

 

(0 = Normal, 1 = Alarm)

R

10242

 

1

Boiler Operation

 

(0 = Firing, 1 = Ready)

R

10243

 

2

Low Water Cutoff

 

(0 = Normal, 1 = Alarm)

R

10244

 

3

Low Pressure Water

 

(0 = Normal, 1 = Alarm)

R

10245

 

4

Low Pressure Gas

 

(0 = Normal, 1 = Alarm)

R

10246

 

5

High Pressure Gas

 

(0 = Normal, 1 = Alarm)

R

10247

 

6

High Limit

 

(0 = Normal, 1 = Alarm)

R

10248

 

7

Thermostat - Operating aquastat (not fault)

(0 = Normal, 1 = Aquastat)

R

10249

 

8

Manual Override

 

(0 = Normal, 1 = Alarm)

R

10250

 

9

Flow Switch

 

(0 = Normal, 1 = Alarm)

R

10251

 

10

No Pilot

 

(0 = Normal, 1 = Alarm)

 

30047

40047

bit

Boiler #4 Status Word

Boiler #4

 

R

10257

 

0

Boiler Not On Line

 

(0 = Normal, 1 = Alarm)

R

10258

 

1

Boiler Operation

 

(0 = Firing, 1 = Ready)

R

10259

 

2

Low Water Cutoff

 

(0 = Normal, 1 = Alarm)

R

10260

 

3

Low Pressure Water

 

(0 = Normal, 1 = Alarm)

R

10261

 

4

Low Pressure Gas

 

(0 = Normal, 1 = Alarm)

R

10262

 

5

High Pressure Gas

 

(0 = Normal, 1 = Alarm)

R

10263

 

6

High Limit

 

(0 = Normal, 1 = Alarm)

R

10264

 

7

Thermostat - Operating aquastat (not fault)

(0 = Normal, 1 = Aquastat)

R

10265

 

8

Manual Override

 

(0 = Normal, 1 = Alarm)

R

10266

 

9

Flow Switch

 

(0 = Normal, 1 = Alarm)

R

10267

 

10

No Pilot

 

(0 = Normal, 1 = Alarm)

 

30048

40048

bit

Boiler #3 Status Word

Boiler #5

 

R

10273

 

0

Boiler Not On Line

 

(0 = Normal, 1 = Alarm)

R

10274

 

1

Boiler Operation

 

(0 = Firing, 1 = Ready)

R

10275

 

2

Low Water Cutoff

 

(0 = Normal, 1 = Alarm)

R

10276

 

3

Low Pressure Water

 

(0 = Normal, 1 = Alarm)

R

10277

 

4

Low Pressure Gas

 

(0 = Normal, 1 = Alarm)

R

10278

 

5

High Pressure Gas

 

(0 = Normal, 1 = Alarm)

R

10279

 

6

High Limit

 

(0 = Normal, 1 = Alarm)

R

10280

 

7

Thermostat - Operating aquastat (not fault)

(0 = Normal, 1 = Aquastat)

R

10281

 

8

Manual Override

 

(0 = Normal, 1 = Alarm)

R

10282

 

9

Flow Switch

 

(0 = Normal, 1 = Alarm)

R

10283

 

10

No Pilot

 

(0 = Normal, 1 = Alarm)

A-3

21

Page 21
Image 21