11.1. Product Specifications

The T-3 card is a hardware product designed to be the communications front end for the Raypak B6000 Boiler Control and a modbus Master Host.

The product includes the following functionality:

Modbus Slave Specifications

Protocol Modes:

RTU mode with CRC-16 error checking

Supported Modbus Function codes:

2Read Input Status

3Read Multiple Data Registers

4Read Input Registers

6

Preset (Write) Single Data Register

8 Loopback Test (Test 0 only)

Supports broadcast commands from host

RS-485 electrical interface

Raypak B6000 Interface

RS-485 electrical interface

Emulates Raypak Modem address and functionality

General Specifications

Configurations via dip switches

Slave Address, Baud and Parity

Hardware Specifications

4” X 5” form factor

Two male 9-pin D Shell connectors

Communications Status lights - Active and Fault for each port

9 to 30 VDC external power