WATER TEMPERATURE SENSOR
•INSTALLATION The water sensor should be installed in the system supply.
Supply
Return
Multiple Boilers
Single Boiler
TYPICAL WATER SENSOR
Water Temperature Sensor Installation Notes:
•Locate sensor in system piping within a minimum of three (3) feet or prior to the first take off connection, on the downstream side of the System Supply Loop.
•Assure cable length does not exceed 4000 ft. Use larger gauge (Belden #9842) wire if run is in excess of 100 ft.
•Install in conduit with no other wiring.
•Observe proper wire colors. Sensor is ploarity sensitive.
Page 10