Raypak B6000 manual COMMUNICATION RS 485 WIRING

Models: B6000

1 51
Download 51 pages 14.6 Kb
Page 13
Image 13
COMMUNICATION (RS 485) WIRING

COMMUNICATION (RS 485) WIRING

System Control

Boiler Monitor

Use Belden #9842 Cable Or Equivalent (See Note). Polarity must be observed. Make use of wire color coding to ensure proper polarity.

The shielding foil wrapper - bare wire (drain) - MUST be grounded.

Grounding is done at the System Control Module only. DO NOT ground at Boiler Monitor.

Note: Equivalent shielded cable must be suitable for RS 485 communication applications; must have 100-140 ohm impedance; and less than 30 picofarad per foot capacitance.

Install in conduit with no other wiring.

BELDEN #9842

NOTE: Tighten terminal strip clamping screws 20 lbs - In (2.26N.m) Breakage from over torquing is not covered under warranty.

Use copper conductors only.

For supply connections use wires sized on the basis of 60°C Ampacity and rated Min. 90°C (194°F).

 

 

 

 

 

 

 

 

 

 

BOILER MONITOR

SYSTEM CONTROL

TERMINAL TB 3

TERMINAL TB2

 

 

RS 485 Communications Cable Schematic

Page 13

Page 13
Image 13
Raypak B6000 manual COMMUNICATION RS 485 WIRING