INSTALL CONDUIT AS APPROPRIATE.

A sub-panel containing the disconnect switches and surge suppressors is required at or near the equipment location(s).

For accessibility remove the lower interior panel, by removing the four (4) access screws.

INSTALL CONDUIT AS APPROPRIATE.

NOTE: Shielded cable, Belden #8132 or #9842 or equivalent, must be used to connect the sensors to the System Control Module.

DIMENSIONS AND WEIGHT

 

System Control Module 19 1/2 lbs

Boiler Monitor Module 21 1/4 lbs

15

3/16 L

17 1/2 L

12

1/2 W

18 3/4 W

4

3/4 D

5 1/2 D

ELECTRICAL CHARACTERISTICS

Control Module - 120 VAC, 0.5A; 60 Hz

Boiler Monitor Module - 120 VAC, 2.0A; 60 Hz

ELECTRICAL INSTALLATION

115 VAC FEEDER CIRCUITS

Install surge protection device(s) sized appropriately for your installation.

Install separate disconnect means for each load. Pull in appropriately sized wire for equipment as defined by NEC and/or local code. All primary wiring will be 125% of minimum rating.

It is strongly recommended that the System Control Module and the Boiler Control Module be supplied from the same source power.

CHECK YOUR POWER SOURCE

Using a volt-ohm meter, check the following voltages at the circuit breaker

Hot

CB

Neutral (Return)

 

 

 

VOM

 

WHITE

 

 

 

GROUND

 

 

BLACK

GREEN

 

 

 

 

 

A B

C

 

 

AC = 108 Volts AC Minimum, 132 Volts MAX Hot to Ground

AB = 108 Volts AC Minimum, 132 Volts MAX Hot to Neutral

BC = Must be less than 1.0 Volts AC

Neutral to Ground