Raypak B6000 manual Troubleshooting Guide, Symptom

Models: B6000

1 51
Download 51 pages 14.6 Kb
Page 48
Image 48

Troubleshooting Guide

The procedures outlined below assume that the initial installation / turn on / power up procedures have been completed and that the B6000 was operational. This guide is a basic instruction to determine if an authorized Raypak representative should be contacted.

If you follow the instructions in this manual and have difficulty operating the B6000, locate the SYMPTOM in the left column below. Check the corresponding POS- SIBLE CAUSE and CORRECTIVE ACTION Column to locate and remedy the problem.

Symptom

Possible Cause

Corrective Action

 

 

 

No Display.

No Primary power.

Check power connections to units.

 

 

Check surge protection devices.

 

 

Check disconnects, check

 

 

grounds.

 

 

Check power switches.

 

 

 

* Nite set-back time display no

Time display accidentally

Initialize system.

longer correct.

Re-Programmed.

Program Nite set-back feature.

 

 

 

* Nite set-back not working

Nite set-back turned off.

Initialize system.

properly.

Clock times not set.

 

 

 

 

* Time display does not maintain

System ground not adequate.

Initialize system and / or

proper time.

Line noise.

contact authorized Raypak

 

Internal battery weak.

Representative for further instruc-

 

Prolonged power outage.

tions.

 

 

 

System not working automatically.

Boiler monitor has Manual Mode

Select Automatic mode on Boiler

 

selected

Monitor.

 

 

 

Display shows incorrect number of

Inadequate grounds.

Check primary power - check

boilers.

Line noise

wired ground.

 

Power outages.

Rework as necessary.

 

 

Initialize system.

 

 

 

Scrambled control display.

Power outages.

Initialize system.

 

 

 

Boiler does not function properly

Internal battery weak.

Initialize system.

after power outage.

Line noise.

 

 

System ground not adequate.

 

 

 

 

Boiler "Not on Line" displayed.

Primary power at boiler not

Initialize system.

 

connected.

 

 

 

 

Outdoor and water temp.

Inadequate ground

Initialize system.

readings Incorrect (-35°F).

Line noise.

 

 

Power outage.

 

 

 

 

Displayed parameters

Power outage.

Initialize system.

do not make sense.

 

 

 

 

 

System Faults indicators do not

Power outage.

Initialize system.

make sense.

 

 

 

 

 

* With Nite Set-Back option only.

 

 

Page 48

Page 48
Image 48
Raypak B6000 manual Troubleshooting Guide, Symptom