Configuration Note:

IMPORTANT

Configuration Note:

If your System Control Module is supplied with a single Field Wiring

Teminal Strip use Teminal Strip use  "Alternate" wiring. (See page 36-38)WIRING - AIR AND WATER SENSORS "Alternate"TO THE SYSTEM CONTROL MODULEManual background wiring. (See page 36-38)

WIRING - AIR AND WATER SENSORS

TO THE SYSTEM CONTROL MODULE

WATER

SENSOR

OUTDOOR

SENSOR

SYSTEM CONTROL

TERMINAL TB 2

BELDEN #8132

OR BELDEN #9842

NOTE: Tighten terminal strip clamping screws 20 lbs - In (2.26N.m) Breakage from over torquing is not covered under warranty.

Use copper conductors only.

For supply connections use wires sized on the basis of 60°C Ampacity and rated Min. 90°C (194°F).