SYSTEM CONTROL/DISPLAY FAMILIARIZATION
The System is set up by using the selector buttons and the displays on the System Control module.
There are ten or more displays. Each display provides information regarding the system operating parameters and system component status. Some displays provide information only, such as current outdoor temperature, system temperature, etc..
Selectable data is identified by flashing characters.
The selector buttons are:
"MENU" - which when pressed will change displays.
"SELECT" - moves the cursor - flashing character - to the next selection in a display. "+" - moves a value to a higher reading (e.g. Display shows flashing boiler #1. Pushing "+" will change display to boiler #2).
EDITING B6000 DISPLAYS LOCATION
The B6000 BMS has a forty (40) character screen that displays status and memory contents.
Selectable Parameters on the B6000 Monitor Screen are as follows:
Selectable Parameters | Range | Value |
| |
Change to Fahrenheit (F) or Celsius (C). | Default (After Initialization) | |||
Maximum Water Temp | 70 | - 235 | Degrees…………180 | |
Set | 40 | - 220 | Degrees…………100 | |
Day Temperature | 40 | - 220 | Degrees…………100 | |
Nite | 40 | - 220 | Degrees………… 90 | |
Ratio | None - 20:1 | Numeric…………1.0:1 | ||
° Rise | 1 | - 99 | Degrees………… 20 | |
Step | 1s,2s, 5 - 100 | Percentile……… | 20 | |
O/C (Outdoor Cutoff) | 35 | - 199 | Degrees………… 65 | |
O/Cdb (O/C dead band) | 1 - 9 | Degrees………… | 4 | |
CBand (Control Band) | 1 | - 9 | Degrees………… | 3 |
Lead | 1 | - 8 | Numeric………… | 1 |
Change Hours | 0 | - 225 | Numeric…………100 | |
Pump Delay * | 0 | - 20 | Minutes………… | 3 |
Ign Time* | 15 | - 100 | Seconds………… 30 |
*Indicates multiple entries
When the B6000 BMS is equipped with a night setback feature, [ WHEN INITIALIZED], NITE SETBACK defaults to OFF.